![Ziton ZP2 Series Скачать руководство пользователя страница 47](http://html2.mh-extra.com/html/ziton/zp2-series/zp2-series_installation-manual_3848886047.webp)
Chapter 3: Configuration and commissioning
ZP2 Series Installation Manual
41
The Panel setup menu
Use the Panel setup menu to set the date and time, to synchronize the date and
time in a fire network, and to set day or night mode sensitivity settings.
Date and time
Select Date and time to change the control panel date and time.
Note:
Additional date and time settings (daylight saving, SNTP polling, etc.) are
available. See “Auto date and time” on page 76.
To change the date and time:
1. Select Panel setup from the Main menu.
2. Select Date and time.
3. Enter the date using the format DD/MM/YY (for example, 10/06/09).
4. Enter the time using the format hh:mm:ss (for example, 15:03:25).
5. If required, select YES for Firenet time sync to synchronize the date and time
across all control panels in a fire network.
6. Press F4 (Enter), and then press F1 (Back).
7. Press F2 (Exit) to exit the menu.
Day/night mode sensitivity settings
Select Day/Night mode to change selected day/night fire detection and response
criteria based on preconfigured time settings, as shown below.
Note:
This option is not available on repeater panels.
Table 17: Day/night mode settings and icons
Mode
LCD icon
Description
Day
In this mode an automatic fire alarm (an alarm activated by a
detector) activates sounders and fire routing (if enabled) after
any configured delay. Subject to configuration, detectors may
use a reduced sensitivity setting.
Night
In this mode an automatic fire alarm (an alarm activated by a
detector) activates sounders and fire routing (if enabled)
immediately and bypasses any configured delay. Subject to
configuration, detectors may use an increased sensitivity setting.
The LCD icon confirming the current mode is displayed on the LCD and indicates
whether the setting applies only to the local control panel or is a general setting
for all control panels in the fire network. For more information on LCD indications,
see “LCD controls and indicators” on page 10.
Setting the day/night schedule
Select Day/Night schedule to configure weekly schedules for day and night mode
settings.
Содержание ZP2 Series
Страница 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Страница 6: ...iv ZP2 Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Страница 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Страница 126: ...Chapter 5 Technical specifications 120 ZP2 Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications ZP2 Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Страница 148: ......