Chapter 3: Configuration and commissioning
92
ZP2 Series Installation Manual
The output group alarm confirmation configuration options are shown in the table
below.
Note:
Configuration requires that two independent alarm confirmations be
selected from the available options and that a confirmation delay (in seconds) is
entered for the corresponding output group to be activated.
Table 53: Output group alarm confirmation options
Option
Description
DEV l.ddd
An alarm activated by a predefined loop and addressable device, where “l”
is the loop number and “ddd” is the device address
ZONE zzzz
An alarm activated by a predefined global zone, where “zzzz” is the global
zone number (from 1 to 9999)
PANEL pp
An alarm activated by a predefined control panel, where “pp” is the control
panel network node ID
ALWAYS
If only a single alarm event with confirmation delay is required (for example
for a manual call point zone), select the corresponding first alarm event, and
then select this option for the second alarm
To configure delayed output group activation:
1. Select Field setup from the Main menu, and then select Output groups.
2. Select Confirmations, and then select the output group to configure.
A list of the available output groups that allow alarm confirmation
configuration is displayed.
3. Select Active, and then select YES (alarm confirmation is required) or NO
(alarm confirmation is not required).
4. Select Alarm1, and then select the confirmation required (DEV, ZONE,
PANEL, or ALWAYS). Repeat this step for Alarm2.
If alarm confirmation is required then the output group is activated only when
both configured alarm confirmation states are detected during the
confirmation delay period.
Extinguishing output group confirmation requires two zones to be configured
for Alarm1 and Alarm2. See note below.
5. Select Delay, and then enter the confirmation delay in seconds (0 to 999).
6. Select EXTnode, and then enter the address of the extinguishing control
panel.
This field is only available when configuring confirmation for an extinguishing
output group.
7. Press F4 (Enter), and then press F1 (Back).
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Содержание ZP2 Series
Страница 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Страница 6: ...iv ZP2 Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Страница 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Страница 126: ...Chapter 5 Technical specifications 120 ZP2 Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications ZP2 Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Страница 148: ......