Chapter 3: Configuration and commissioning
ZP2 Series Installation Manual
79
Zone configuration
Zone configuration options are shown in the table below.
Table 40: Zone configuration options
Option
Description
General config
Configures the initial zone, the initial zone for a zone LED indicator (if an
optional zone indicator board is installed), the maximum number of
zones in test, and the number of global zones.
Zone config
Configures additional zone settings, such as the zone type (normal or
confirmed with corresponding parameters), area, CIT and ACT delays,
disabled or enabled, operation mode, etc.
Area config
Configures areas. An area is a group of zones used for alarm
confirmation.
Test/Disable t_out
Configures the zone test or disable timeout period. See “Zone test and
disablement timeout” on page 40 for more information.
Zone overview
The maximum number of zones available is 512 (for all control panels). The zone
number range is 01 to 9999.
Note:
For 2010-2GUI application compatibility, assigned zone numbers must be
in the range 1 to 4095 (zones with higher numbers will be discarded).
Zones in networked control panels are considered global. If two networked
control panels each include, for example, Zone 5, then these are grouped to
create a single Zone 5 configuration within the network.
Remote zones
The control panel also considers an additional zone called remote zone (REMT)
which spans all the zones in the system outside the control panel zones range.
This virtual zone can be configured like any other zone in the system and it is
important to define output group activation requirements when the panel receives
remote alarms.
Assigning loop devices to zones
Create zones by assigning zone numbers to loop devices.
To assign a zone number to a loop device:
1. Select Field setup from the Main menu.
2. Select Loop device configuration.
3. Select the corresponding loop and device.
4. Assign a zone number to the device.
5. Press F4 (Enter), and then press F1 (Back).
Содержание ZP2 Series
Страница 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Страница 6: ...iv ZP2 Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Страница 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Страница 126: ...Chapter 5 Technical specifications 120 ZP2 Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications ZP2 Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Страница 148: ......