Chapter 3: Configuration and commissioning
54
ZP2 Series Installation Manual
Table 20: Control panel configuration
Option
Description
ID configuration
Configures the control panel Firenet ID (for the fire network) and
description. The description is displayed on the LCD when the
control panel is in standby.
Date and time
Configures the control panel date and time, and to synchronize the
date and time in a fire network. See “Date and time” on page 41.
Day/Night mode
Configures the sensitivity settings for the day/night schedule and
for the holiday calendar. See “Day/night mode sensitivity settings”
on page 41.
Regional options
Configures the control panel's regional operation mode.
Firenet
Configures the control panel fire network.
Communications
Configures TCP/IP communication settings, to manage email
accounts (for event notifications), and to safely remove a USB
device.
Other settings
Configures general panel settings, including 24V AUX output, fault
mask, sounder re-sound, school bell settings, etc.
Load/Save configuration
Loads a new configuration, saves the current configuration file to a
USB flash drive, restores the previous configuration, or restores the
default factory settings.
Expansion boards
Configures any installed expansion boards.
Load auxiliary files
Loads auxiliary files from a USB flash drive. Auxiliary files that can
be loaded include custom standby and alarm screens, and updated
language or font files for extended language support.
System update
Loads control panel firmware updates.
Printer configuration
Configures external and internal printer settings.
DACT configuration
Configures Ethernet, central monitoring station, PSTN, and GPRS
settings for an installed DACT board.
Panel Activation Key
Registers or unregisters panel activation keys (PAKs).
Auto Date and Time
Configures additional date and time settings, including SNTP,
daylight saving, and time zone.
BMS Config [1]
Configures building management protocol settings (BACnet ®,
Modbus ®).
[1] Use of BACnet or Modbus requires the corresponding PAK to be registered at the gateway
panel.
ID configuration
Select ID configuration to configure the control panel Firenet ID (for the fire
network) and description. The default ID is 001.
Note:
The allowed ID range is defined by the size of the fire network. The default
range is 001 to 032, but the range increases if the size of your network is
extended using a panel activation key (PAK). See “Panel activation key” on page
75.
Содержание ZP2 Series
Страница 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Страница 6: ...iv ZP2 Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Страница 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Страница 126: ...Chapter 5 Technical specifications 120 ZP2 Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications ZP2 Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Страница 148: ......