Chapter 3: Configuration and commissioning
ZP2 Series Installation Manual
93
Note
A remote extinguishing panel can be configured to receive extinguishing
preactivate and activate commands associated with the local extinguishing
output group confirmation.
When one of the two configured confirmation zones (Alarm1, Alarm2) enters into
alarm, the preactivate command is sent to the extinguishing panel (EXTnode).
When the second zone enters into alarm, the activate command is sent to the
extinguishing panel.
Assigning an output group to a programmable button
Note:
This option is not available for control panels in regional mode VdS 2540.
For fire alarm control panels, one output group can be assigned to the
programmable button and LED on the control panel interface for control and
indication. See Figure 1 on page 4 for the location of the programmable button
and LED.
For evacuation panels, up to seven output groups can be assigned to the
programmable buttons and LEDs. See Figure 2 on page 5 for the location of the
programmable buttons and LEDs
By default, all programmable buttons are set to sounder group 1.
Note:
Evacuation panels operating in NEN 2575 mode can only assign sounder
output groups to the programmable buttons. Evacuation panels operating in other
modes can assign any of the available output group types to the buttons.
Remember to create the output groups that you need before configuring the
programmable buttons. See “Output groups” on page 89 for more information.
To assign an output group to a programmable button:
1. Select Field setup from the Main menu, and then select Output groups.
2. Select Progr. Controls.
3. Select the button/LED to configure.
For evacuation panels, the programmable buttons are numbered #1 to #7, top
to bottom.
4. Select and check In Use.
5. Select OpMode, and then select the output group mode.
6. Select Group_n, and then enter the number of the output group that you want
to assign to the button.
7. Select Delay, and then enter any required confirmation delay (in seconds).
The delay counts down after the Confirm button is pressed before activating
the assigned output group. The maximum delay value is 600 seconds.
8. Press F4 (Enter), and then press F1 (Back).
Содержание ZP2 Series
Страница 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Страница 6: ...iv ZP2 Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Страница 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Страница 126: ...Chapter 5 Technical specifications 120 ZP2 Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications ZP2 Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Страница 148: ......