Form No. F_102011

AMX5000

Aspirating smoke detector

From production number 060608 and SW version 01.02.01

The AMX5000 aspirating smoke detector performs the task of
taking continuous air samples via one or two sampling pipe net-
works from a monitored area and feeding the samples to one
or two smoke sensors.

The AMX5000 consists of the detector housing and one or two
sampling pipe tube networks. The sampling pipes have several
sampling holes whose size is such that each hole draws the
same amount of air. The sampling pipes may be I-, U-, T-, H-,
or E-shaped. The sampling pipes are usually symmetrically de-
signed. Asymmetrical sampling pipe tube networkscan also be
implemented using the “HELIOS PipeCalc” calculation soft-
ware.

Description

You find all necessary Information for setting up
AMX5000 fire alarm systems in the short instruction;
for the complete information and specifications refer to
the Technical Description AMX5000, FHB 34 (908146)

Integrated in the detector housing is a high-speed fan which, in
conjunction with the sampling pipe, ensures uninterrupted air
supply to the detector housing. Airflow monitoring detects any
block-ages or breaks in each of the sampling pipe networks.
The AMX5000 is available in four versions: 

AMX5001

for 1 sampling tube, and 1 smoke sensor
without smoke level indicator;

AMX5002

for 2 sampling tubes, and 2 smoke sensors
without smoke level indicator;

AMX5101

for 1 sampling tube, and 1 smoke sensor
with smoke level indicator;

AMX5102

for 2 sampling tubes, and 2 smoke sensors
with smoke level indicator.

The AMX5000 can be equipped with the following smoke sen-
sor types:

OMX5005

Sensitivity range 0.5%/m to 10%/m 
(0.15%/ft to 3.15%/ft)

OMX5010

Sensitivity range 0.1%/m to 10%/m
(0.03%/ft to 3.15%/ft)

OMX5020

Sensitivity range 0.02%/m to 10%/m
(0.006%/ft to 3.15%/ft)

The AMX5000 aspirating smoke detector has four slots for ex-
pansion modules. The following modules can be added:

KMX5005 RK  Relay Interface Module with 5 relays (max.

2 units);

MMX5005

Memory module

Other

In preparation (interface module)

The AMX5000 can be linked to a higher level FACP by means
of relays.

The AMX5000 can be connected to a fire alarm system by
using potential free contacts.

Integration in the System FMZ5000 Loop Ap is possible by mo-
dules. Displaying status and control of the AMX device can
thus be performed directly from the FACP.

Fig. 1  AMX5102

A further expansion option is the KMX5005 RK Relay Interface
Module. This module enables the availability of all three pre-si-
gnal levels as well as the states “smoke sensor dirty” and “LS-
Ü blockage” as relay contacts. The relays are also freely confi-
gurable via the HELIOS Config configuration software. 

The MMX5005 Memory module serves to record operating data. 

The AMX5000 aspirating smoke detector can be used for:

Equipment monitoring:

 EDP systems, electrical distributors,

switch cabinets, etc.

Space surveillance:

 EDP rooms, clean rooms, warehouses,

high-rack storage buildings, hollow floors, protection of cul-
tural objects, transformer stations, prison cells, etc.

The AMX5000 is also deployed in areas where conventional
point type detectors are used. The local provisions and regula-
tions must be observed from case to case.

The response behavior of the AMX5000 has been tested in
compliance with EN 54-20, Class A, B and C (or NFPA 72). 

When setting up AMX5000 fire alarm systems, the in-
formation and specifications in 

“Technical Descripti-

on AMX5000” 

must be observed and adhered to.

This includes among others: 

General

Section 1

Planning

Section 4

Mounting

Section 5

Installation

Section 6

Commissioning

Section 7

Opening the detector housing

Press the rotary snap locks firmly with the screwdri-
ver (min. No. 5) toward the housing base and then
turn 90°. The position of the lock slit shows the cur-
rent state: 

approx. 45° angled toward detector housing corner
= closed

approx. 45° angled toward detector housing edge

 = 

open

The rotary snap locks must snap into place.

The housing cover (control unit) is connected to the Main Board
by a flat cable. Make sure that when the housing cover is lifted
away the flat cable does not become damaged.

 

Содержание AMX5000 Series

Страница 1: ... modules can be added KMX5005 RK Relay Interface Module with 5 relays max 2 units MMX5005 Memory module Other In preparation interface module The AMX5000 can be linked to a higher level FACP by means of relays The AMX5000 can be connected to a fire alarm system by using potential free contacts Integration in the System FMZ5000 Loop Ap is possible by mo dules Displaying status and control of the AM...

Страница 2: ...ning is prevented by the anti twist rib on the smoke sensor housing The smoke sensors are fastened with the two lock clamps in the AMX housing The electrical connection to the Main Board is accomplished with the supplied ribbon cable The smoke sensor chamber II on the AMX5001 and AMX5101 only one smoke sensor remains open insect protection screens and lock clamps are not fitted air channels are cl...

Страница 3: ...n Alarm Fault Det dusty dirty Smoke level green red yell yell yell System off no voltage System inactive external reset On 1 2 T Smoke sensor off from FACP On 1 2 T Idle state On Blockage pipe breakage delay time running On 1 T Blockage pipe breakage fault triggered On On Fan tacho signal lacking On On Fault triggered On On Pre signal 1 AMX5001 5002 On 2 T Pre signal 2 AMX5001 5002 On 1 T Pre sign...

Страница 4: ... AMX to the last T piece cross Max length from AMX to the farthes sampling hole Number of sampling holes per sampling branch Max total length of the sampling pipe per pipe network smoke sensor 1 tube 2 tube 1 tube 2 tube I 1 A11 A12 W01 W04 W05 W08 20 0 03 0 01 50 m 164 ft 1 7 50 m 164 ft U T 1 A11 A12 W01 W04 W05 W08 20 0 03 0 01 3 3 65 6 1 20 m 40 m 131 ft 1 4 80 m 262 ft H 1 A11 A12 W01 W04 W05...

Страница 5: ...4 0 7 0 12 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 13 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 14 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 4 0 7 0 15 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 4 0 7 0 16 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 4 0 7 0 U T shaped sampling pipes Number of sampling holes per sampling branch Hole diameter in mm for th...

Страница 6: ...of Al 75 65 90 5 X01 X03 Dust self hold On On Off X01 X03 Dirt self hold On On Off X01 X03 Fault delay of smoke sensor 30 s 0 s 60 s 1 s X01 X03 Airflow monitoring LS Ü blockage On Off On On Off X01 X03 LS Ü pipe breakage On Off On On Off X01 X03 LS Ü sensitivity 20 10 70 10 X01 X03 LS Ü average value formation 20 s 1 30 s 1 s X01 X03 LS Ü delay time 300 s 2 min 60 min 10 s 1 min X01 X03 The defau...

Страница 7: ... dirty Relay 5 2nd KMX5005 RK Sampling tube II pipe blockage Reset button On Off On On Off Start initial reset On Off Relay allocation configuration options The following criteria can be programmed on a max of 11 relays 1 Main Board unit on AMX5001and AMX5101 6 units on 1st KMX5005 RK 5 units on 2nd KMX5005 RK Smoke sensor I LS Ü I Smoke sensor II LS Ü II General Smoke sensor I alarm Smoke sensor ...

Страница 8: ... is now ready for operation Re programming Example Response class B system limit 2 AMX5102 2 sam pling tubes required switch setting b22 Initial reset Measurements commissioning protocol Carry out the following measurements Measure operating voltage on terminals 1 2 if redun dant supply then also terminals 3 4 target value 12 3 to 13 8 VDC in 12 VDC operation or 21 6 to 27 6 VDC in 24 VDC operatio...

Страница 9: ...be car ried out for both sampling pipes Brief description Article number Aspirating smoke detector AMX5001 908095 Aspirating smoke detector AMX5002 908096 Aspirating smoke detector AMX5101 908097 Aspirating smoke detector AMX5102 908098 Smoke sensor OMX5005 0 5 m 10 m 0 15 ft 3 15 ft 908099 Smoke sensor OMX5010 0 1 m 10 m 0 03 ft 3 15 ft 908100 Smoke sensor OMX5020 0 02 m 10 m 0 006 ft 3 15 ft 908...

Страница 10: ... IEC 529 EN 60529 1991 54 IP Ambient conditions acc to IEC 721 3 3 EN 60721 3 3 1995 3K5 3Z1 Class Extended ambient conditions Detector housing temperature range 30 60 4 140 C F Sampling pipe temperature range 30 60 4 140 C F Max approved temperature fluctuation in detector housing and sampling pipe operation 20 68 C F Max storage temperature deflector housing no condensation 30 70 4 158 C F Ambie...

Отзывы: