background image

4 / 10

FHK34, 908143

AMX5000

Short instruction

System limits without “HELIOS PipeCalc”calculation

The system limits apply to planning without the“HELIOS Pipe-
Calc” calculation software. There are two areas with the fol-
lowing meaning: 

Normative system limits

 compliant to EN 54-20, Class A

to C (or NFPA 72), switch settings 

A11

 to 

C32

;

Non-Normative system limits,

switch settings 

W01

 to 

W48

.

Normative system limits

Switch settings 

A11

 to 

C32

 have configured values which are

necessary for alarm response sensitivity and airflow monitoring
compliance with EN 54-20 Class A to C (or NFPA 72). The
switch setting designation is deciphered as follows: 

First figure 

Response class 

A

b

C

 compliant with EN

54-20 (or NFPA 72);

Second figure  System limit 

1

2

3

 (pipe topology);

Third figure 

Number of pipe networks 

1

2

 on the AMX.

Example: 

b22

Response class 

b

 / system limit 

2

 / 

 

2

 pipe networks.

Non-normative system limits

Switch settings 

W01

 to 

W48

 contain system limits which fulfill

only

 the alarm response sensitivity for EN 54-20 Class A to C

(or NFPA 72) 

but not

 the normative limits concerning airflow

monitoring. Since these are identical to system limits 

A11

 to

C32

 concerning pipe topology (pipe network length, number of

sampling holes), switch settings 

W01

 to 

W48

 are also included

in the tables below in section 4.4.4.3. Additional information
about switch settings 

W01

 to 

W48

 concerning number of pipe

networks and airflow monitoring can be found in Technical De-
scription FHB 34 (908142), section 4.4.4.4.

Switch settings 

W01

 to 

W48

 may be used only after

consulting with the manufacturer. The configured va-
lues theycontain concerning airflow monitoring are

not

 tested inaccordance with EN (or NFPA 72). 

                Further information about using the system limits

table is found in Technical Description FHB 34
(908142), sections 4.4.4.3 and 4.4.4.4.

System limits table for planning without “HELIOS PipeCalc” calculation
EN 54-20 compliance, Class A (highly sensitive) (or NFPA 72)

Sha

p

e

S

y

stem

 limit

S

w

it

ch set

tin

g

to

 EN

 5

4

-2

0

(o

r N

F

PA 72)

S

w

it

ch set

tin

g

No

n-

norm

a

tive

Smok

e senso

r

typ

e

 OMX50x

x

Ala

rm

 th

resho

ld

/ m (% / ft)

L

e

ng

th

 f

rom

 A

M

X

to

 t

h

e last

T-p

iece/cro

s

s

Max. len

g

th fr

o

m

A

M

X to 

the f

a

rth

e

s

sam

plin

g h

o

le

Nu

mbe

r o

f sam

plin

g

ho

les per sa

mpl

ing

bran

ch

Max. tota

l leng

th o

f

th

e s

a

m

pl

in

g p

ipe

per p

ipe n

e

tw

ork

(sm

o

ke sen

sor)

1 tube 2 tube

1 tube

2 tube

I

1

A11

A12

W01 – W04 W05 – W08

20

0.03 (0.01)

---

50 m (164 ft)

1 – 7

50 m (164 ft)

U / T 1

A11

A12

W01 – W04 W05 – W08

20

0.03 (0.01)

3’-3”– 65’-6” (1 – 20 m) 40 m (131 ft)

1 – 4

80 m (262 ft)

H

1

A11

A12

W01 – W04 W05 – W08

20

0.03 (0.01)

3’-3”– 65’-6” (1 – 20 m) 40 m (131 ft)

1 – 2

100 m (328 ft)

E

1

A11

A12

W01 – W04 W05 – W08

20

0.03 (0.01)

3’-3”– 65’-6” (1 – 20 m) 40 m (131 ft)

1 – 3

100 m (328 ft)

EN 54-20 compliance, Class B (sensitive) (or NFPA 72)

I

1

b11

b12

W09 – W12 W13 – W16

20

0.09 (0.03)

---

50 m (164 ft)

1 – 7

50 m (164 ft)

2

b21

b22

W17 – W20 W21 – W24

20

0.06 (0.02)

---

70 m (229 ft)

5 – 9

70 m (229 ft)

U / T

1

b11

b12

W09 – W12 W13 – W16

20

0.09 (0.03)

3’-3”– 65’-6” (1 – 20 m) 40 m (131 ft)

1 – 3

80 m (262 ft)

2

b21

b22

W17 – W20 W21 – W24

20

0.06 (0.02)

3’-3”– 65’-6” (1 – 20 m) 55 m (180 ft)

3 – 5

110 m (360 ft)

H

1

b11

b12

W09 – W12 W13 – W16

20

0.09 (0.03)

3’-3”– 65’-6” (1 – 20 m) 35 m (114 ft)

1 – 2

140 m (459 ft)

2

b21

b22

W17 – W20 W21 – W24

20

0.06 (0.02)

3’-3”– 65’-6” (1 – 20 m) 455 m (147 ft) 2 – 3

140 m (459 ft)

E

1

b11

b12

W09 – W12 W13 – W16

20

0.09 (0.03)

3’-3”– 65’-6” (1 – 20 m) 40 m (131 ft)

1 – 2

120 m (393 ft)

2

b21

b22

W17 – W20 W21 – W24

20

0.06 (0.02)

3’-3”– 65’-6” (1 – 20 m) 50 m (164 ft)

2 – 3

140 m (459 ft)

EN 54-20 compliance, Class C (standard) (or NFPA 72)

I

1

C11

C12

W25 – W28 W29 – W32

05

0.8 (0.266)

---

40 m (131 ft)

1 – 5

40 m (131 ft)

2

C21

C22

W33 – W36 W37 – W40

10

0.35 (0.116)

---

80 m (262 ft)

3 – 9

80 m (262 ft)

3

C31

C32

W41 – W44 W45 – W48

10

0.13 (0.043)

---

110 m (360 ft) 7 – 16 110 m (360 ft)

U / T

1

C11

C12

W25 – W28 W29 – W32

05

0.8 (0.266)

1 – 20 m (3’-3”– 65’-6”)

30 m (98 ft)

1 – 3

60 m (196 ft)

2

C21

C22

W33 – W36 W37 – W40

10

0.35 (0.116) 1 – 20 m (3’-3”– 65’-6”) 60 m (196 ft)

3 – 5

120 m (393 ft)

3

C31

C32

W41 – W44 W45 – W48

10

0.13 (0.043) 1 – 20 m (3’-3”– 65’-6”) 70 m (229 ft)

5 – 9

140 m (459 ft)

H

1

C11

C12

W25 – W28 W29 – W32

05

0.8 (0.266) 1 – 25 m (3’-3”– 82’-

1

/

4

”) 35 m (114 ft)

1 – 2

140 m (459 ft)

2

C21

C22

W33 – W36 W37 – W40

10

0.35 (0.116) 1 – 25 m (3’-3”– 82’-

1

/

4

”) 45 m (147 ft)

2 – 3

180 m (590 ft)

3

C31

C32

W41 – W44 W45 – W48

10

0.13 (0.043) 1 – 25 m (3’-3”– 82’-

1

/

4

”) 60 m (196 ft)

3 – 5

200 m (656 ft)

E

1

C11

C12

W25 – W28 W29 – W32

05

0.8 (0.266)

1 – 20 m (3’-3”– 65’-6”)

30 m (98 ft)

1 – 2

90 m (295 ft)

2

C21

C22

W33 – W36 W37 – W40

10

0.35 (0.116) 1 – 20 m (3’-3”– 65’-6”) 50 m (164 ft)

2 – 3

150 m (492 ft)

3

C31

C32

W41 – W44 W45 – W48

10

0.13 (0.043) 1 – 20 m (3’-3”– 65’-6”) 60 m (196 ft)

3 – 6

180 m (590 ft)

 

 

Содержание AMX5000 Series

Страница 1: ... modules can be added KMX5005 RK Relay Interface Module with 5 relays max 2 units MMX5005 Memory module Other In preparation interface module The AMX5000 can be linked to a higher level FACP by means of relays The AMX5000 can be connected to a fire alarm system by using potential free contacts Integration in the System FMZ5000 Loop Ap is possible by mo dules Displaying status and control of the AM...

Страница 2: ...ning is prevented by the anti twist rib on the smoke sensor housing The smoke sensors are fastened with the two lock clamps in the AMX housing The electrical connection to the Main Board is accomplished with the supplied ribbon cable The smoke sensor chamber II on the AMX5001 and AMX5101 only one smoke sensor remains open insect protection screens and lock clamps are not fitted air channels are cl...

Страница 3: ...n Alarm Fault Det dusty dirty Smoke level green red yell yell yell System off no voltage System inactive external reset On 1 2 T Smoke sensor off from FACP On 1 2 T Idle state On Blockage pipe breakage delay time running On 1 T Blockage pipe breakage fault triggered On On Fan tacho signal lacking On On Fault triggered On On Pre signal 1 AMX5001 5002 On 2 T Pre signal 2 AMX5001 5002 On 1 T Pre sign...

Страница 4: ... AMX to the last T piece cross Max length from AMX to the farthes sampling hole Number of sampling holes per sampling branch Max total length of the sampling pipe per pipe network smoke sensor 1 tube 2 tube 1 tube 2 tube I 1 A11 A12 W01 W04 W05 W08 20 0 03 0 01 50 m 164 ft 1 7 50 m 164 ft U T 1 A11 A12 W01 W04 W05 W08 20 0 03 0 01 3 3 65 6 1 20 m 40 m 131 ft 1 4 80 m 262 ft H 1 A11 A12 W01 W04 W05...

Страница 5: ...4 0 7 0 12 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 13 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 2 5 4 0 7 0 14 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 2 5 4 0 7 0 15 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 2 5 4 0 7 0 16 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 0 2 5 4 0 7 0 U T shaped sampling pipes Number of sampling holes per sampling branch Hole diameter in mm for th...

Страница 6: ...of Al 75 65 90 5 X01 X03 Dust self hold On On Off X01 X03 Dirt self hold On On Off X01 X03 Fault delay of smoke sensor 30 s 0 s 60 s 1 s X01 X03 Airflow monitoring LS Ü blockage On Off On On Off X01 X03 LS Ü pipe breakage On Off On On Off X01 X03 LS Ü sensitivity 20 10 70 10 X01 X03 LS Ü average value formation 20 s 1 30 s 1 s X01 X03 LS Ü delay time 300 s 2 min 60 min 10 s 1 min X01 X03 The defau...

Страница 7: ... dirty Relay 5 2nd KMX5005 RK Sampling tube II pipe blockage Reset button On Off On On Off Start initial reset On Off Relay allocation configuration options The following criteria can be programmed on a max of 11 relays 1 Main Board unit on AMX5001and AMX5101 6 units on 1st KMX5005 RK 5 units on 2nd KMX5005 RK Smoke sensor I LS Ü I Smoke sensor II LS Ü II General Smoke sensor I alarm Smoke sensor ...

Страница 8: ... is now ready for operation Re programming Example Response class B system limit 2 AMX5102 2 sam pling tubes required switch setting b22 Initial reset Measurements commissioning protocol Carry out the following measurements Measure operating voltage on terminals 1 2 if redun dant supply then also terminals 3 4 target value 12 3 to 13 8 VDC in 12 VDC operation or 21 6 to 27 6 VDC in 24 VDC operatio...

Страница 9: ...be car ried out for both sampling pipes Brief description Article number Aspirating smoke detector AMX5001 908095 Aspirating smoke detector AMX5002 908096 Aspirating smoke detector AMX5101 908097 Aspirating smoke detector AMX5102 908098 Smoke sensor OMX5005 0 5 m 10 m 0 15 ft 3 15 ft 908099 Smoke sensor OMX5010 0 1 m 10 m 0 03 ft 3 15 ft 908100 Smoke sensor OMX5020 0 02 m 10 m 0 006 ft 3 15 ft 908...

Страница 10: ... IEC 529 EN 60529 1991 54 IP Ambient conditions acc to IEC 721 3 3 EN 60721 3 3 1995 3K5 3Z1 Class Extended ambient conditions Detector housing temperature range 30 60 4 140 C F Sampling pipe temperature range 30 60 4 140 C F Max approved temperature fluctuation in detector housing and sampling pipe operation 20 68 C F Max storage temperature deflector housing no condensation 30 70 4 158 C F Ambie...

Отзывы: