16
IM 54051-E
16
16
3 Setting Up with the Main Unit
■
Batch-setting the alarm function
The following procedure is used to set the
same alarm function for all tags.
Home screen
18:54:27
222
222
25.9
°
C
1.
Press the [FUNC], [7], and [1] keys, in
this order.
The “All File” screen appears on the LCD.
F71
A l l F i l e
2.
Press the [SET] key.
A screen for setting the alarm HIGH function ON/
OFF will appear.
Hi Alarm
ON
3.
Use either the [
▼
] or [
▲
] key to set the
upper-limit temperature alarm function
ON/OFF.
4.
If ON has been selected, press the [SET]
key.
The “Hi Alarm” setting screen will appear on the
screen.
If OFF has been selected in step 3, this screen will
not appear. In this case proceed to step 6.
Hi Alarm
+ 0 0 0 . 0
°
C
5.
Enter the upper-limit temperature.
Hi Alarm
+ 0 2 0 . 0
°
C
[TIP]
To set a negative value, press either the [
▼
] or
[
▲
] key. The “+” symbol on the screen will
change to a “-” symbol.
See Also
For the method of entering a character or num-
ber, refer to “6 How to Input Characters” in
the “Information Required before Use” part.
6.
Press the [SET] key.
The specified upper-limit temperature is set and the
screen of selecting ON/OFF of the “Lo Alarm” func-
tion will appear on the screen.
Lo Alarm
ON
7.
Use either the [
▼
] or [
▲
] key to select
ON/OFF of the lower-limit temperature
alarm function.
8.
When ON has been selected, press the
[SET] key.
The “Lo Alarm” setting screen will appear on the
screen.
If OFF has been selected in step 7, this screen will
not appear. In this case proceed to step 10.
Lo Alarm
+ 0 0 0 . 0
°
C