When disabled, the PROFIBUS interface operates as passive DP slave with the following
characteristics:
n
The PROFIBUS interface gets an "passive" PROFIBUS node, this means it is not
involved in the token rotation.
n
Bus rotation time is not influenced.
n
S7 routing is not possible.
11.3 Enable bus functionality via VSC
11.4 Hardware configuration - CPU
The configuration of the CPU takes place at the Siemens
‘hardware configurator’
. The
hardware configurator is part of the Siemens SIMATIC Manager. It serves for project engi-
neering. Please use for configuration the Siemens SIMATIC Manager V 5.5 SP2 and up.
The modules, which may be configured here are listed in the hardware catalog. If neces-
sary you have to update the hardware catalog with
‘Options
è
Update Catalog’
.
For project engineering a thorough knowledge of the Siemens SIMATIC
Manager and the Siemens hardware configurator is required!
With the Siemens SIMATIC Manager the following steps should be executed:
1.
Start the Siemens hardware configurator with a new project.
2.
Insert a profile rail from the hardware catalog.
3.
Place at
‘Slot’
-Number 2 the CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3).
The integrated PROFIBUS DP master (X3) is to be configured and connected via the sub
module X1 (MPI/DP).