3.
At
‘Properties
è
PROFINET interface...
è
General’
create with
‘Add ne subnet’
a
new sub net and assign valid IP address data.
CAUTION!
Please configure the diagnostic addresses of the CP343-1EX30 for
‘PROFINET interface’
,
‘Port1’
and
‘Port2’
so that no overlaps
occur in the periphery input area. Otherwise your CPU can not
start-up and you receive the diagnostic entry 0xE904. Address
overlaps are not recognized in the Siemens TIA Portal.
4.
After installing the GSDML the
‘PN I-Device for VIPA CPU’
can be found in the
hardware catalog at
‘Other field devices
è
PROFINET IO
è
I/O
è
VIPA GmbH
è
VIPA SLIO System
è
Head module’
. Connect the slave system to the CP 343-1
by dragging&dropping it from the hardware catalog to the
Network view
and con-
necting it to the CP 343-1.
5.
Click in the
Network view
at the PN I-Device and switch to the
Device overview
.
6.
Activate the
‘Filter’
in the hardware catalog.
VIPA System SLIO
Configuration with TIA Portal
TIA Portal - Deployment PG/OP communication - PROFINET > Deployment as PROFINET I-Device
HB300 | CPU | 013-CCF0R00 | en | 19-30