![YASKAWA VIPA System SLIO Скачать руководство пользователя страница 239](http://html.mh-extra.com/html/yaskawa/vipa-system-slio/vipa-system-slio_manual_907132239.webp)
10.4.2
Installing the GSDML file
The following GSDML files are required for configuring the integrated PROFINET IO con-
troller of the VIPA CPU as I-Device in the Siemens SIMATIC Manager:
n
GSDML for I-Device
n
GSDML for I-Device at IO controller
1.
You can find the GSDML files in the download area of www.vipa.com. Load the file
and unzip it on your PC.
2.
Start the Siemens SIMATIC Manager and install via
‘Options
è
Install new GSD file’
both GSD files.
ð
After the installation you can find the following virtual devices in the
hardware
catalog
at
‘PROFINET IO
è
Additional field devices
è
...
è
VIPA SLIO System’
:
n
PN I-Device for VIPA CPU
–
This allows you to configure the Input/output areas in the I-Device of the
VIPA CPU.
n
PN I-Device for higher-level CPU
–
This allows you to connect the VIPA I-Device to the higher-level IO con-
troller.
10.4.3
Configuration as I-Device
It is assumed that a hardware configuration of the CPU exists.
1.
For the project engineering of PROFINET I-Device you have to search the virtual
device
‘PN I-Device for VIPA CPU’
in the hardware catalog at
PROFINET-IO
and
drag&drop it in the PROFINET subnet.
Proceeding
VIPA System SLIO
Deployment PG/OP communication - PROFINET
Deployment as PROFINET I-Device > Configuration as I-Device
HB300 | CPU | 013-CCF0R00 | en | 19-30
239