2.
For the project engineering of the VIPA I-Device in the high-level IO controller you
have to search the device
‘PN I-Device config for higher-level CPU’
in the hardware
catalog at
PROFINET-IO
drag it to
Network view
and connect it via PROFINET to
the CPU.
3.
In the
‘Network view’
, click on the
‘PN-I-Device’
and enter at
‘Device name’
the
previously noted name of the VIPA I-Device.
The configured name must match the name of the CP 343-1 inter-
face of the I-Device CPU, which you have written down before!
Chap. 13.6.2.3 ‘Configuration as I-Device’ page 312
4.
Configure an input area of the same size for each output area of the I-Device in the
IO controller and vice versa. Here also no gaps may arise. In particular, make sure
that the order of the transfer areas matches that of the I-Device configuration. The
following transfer units are available:
n
Input: 1, 8, 16, 32, 64, 128, 256, 512 byte per slot
n
Output: 1, 8, 16, 32, 64, 128, 256, 512 byte per slot
5.
Save and transfer your project to the CPU.
ð
Your VIPA PROFINET controller is now connected as an I-Device to the higher-
level PROFINET IO controller.
VIPA System SLIO
Configuration with TIA Portal
TIA Portal - Deployment PG/OP communication - PROFINET > Deployment as PROFINET I-Device
HB300 | CPU | 013-CCF0R00 | en | 19-30
315