![YASKAWA VIPA System SLIO Скачать руководство пользователя страница 213](http://html.mh-extra.com/html/yaskawa/vipa-system-slio/vipa-system-slio_manual_907132213.webp)
You can use the CMD auto commands WEBVISU_PGOP_ENABLE and
WEBVISU_PGOP_DISABLE to enable or disable the WebVisu. After a
power cycle or loading a hardware configuration, the settings are
retained. With reset to the factory settings or over all reset, the WebVisu
project is set to the default value "enabled".
8.4 Access to the WebVisu
n
When connected via Ethernet PG/OP channel, you have access to the
WebVisu
and
Device web page
of the CPU, controlled via ports.
n
Access to the
WebVisu
can be password-protected and encrypted by means of SSL
certificates. If you want to use SSL certificates, you must integrate them in the
SPEED7 Studio
accordingly.
n
You can create users in the
SPEED7 Studio
via
‘WebVisu project > User
administration’
, who can access the
WebVisu
.
n
Via
‘Device properties > WebVisu configuration’
you can specify the port, the
Web-
Visu
can be accessed and upload SSL certificates. This changes the port for
accessing the device web page.
–
Port number
: 8080 (default): The
WebVisu
can be accessed via the IP address
and port 8080. The
Device web page
can be accessed via the IP address and
port 80.
–
Port number
: 80: The
WebVisu
can be accessed via the IP address and port 80.
The
Device web page
can be accessed via the IP address and port 8080.
–
SSL port number 443 (default): The secure access to the
WebVisu
takes place
via the IP address and port 443. The
Device web page
can be accessed via the
IP address and port 8080.
–
Please note that once you have made adjustments to the user man-
agement, you will need to restart your web browser. Otherwise you
receive system-related error messages about invalid user informa-
tion!
–
Please note that the encryption of the communication can affect CPU
performance and therefore the response time of the entire system!
8.4.1 Status of the WebVisu
On the device web page at the tab
‘WebVisu’
via
‘Status’
you get the status of your
WebVisu
Chap. 4.11.1.1.2 ‘Tab: ‘WebVisu’ ’ page 98
VIPA System SLIO
Deployment WebVisu - Web visualization
Access to the WebVisu > Status of the WebVisu
HB300 | CPU | 013-CCF0R00 | en | 19-30
213