4.7.1.1
Configuration via integrated CPU interface
From firmware version V2.4.0 this variant for configuration is recommended. The fol-
lowing advantages result:
n
The configuration becomes clearer, because the periphery modules and the
PROFINET IO devices are configured on the PROFINET line of the CPU and no addi-
tional CP is to be configured.
n
There are no address collisions, because the S7 addresses for all components are
assigned from the address area of the CPU.
Unless during the hardware configuration of the CPU
assigned yet or these are to be changed, the configuration happens to the following pro-
ceeding, otherwise the Ethernet PG/OP channel is configured.
1.
Open the Siemens hardware configurator and, if not already done, configure the
Siemens CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3).
2.
Open the PROFINET Properties dialog box of the CPU by double-clicking
‘PN-IO’
.
3.
Click at
‘General’
.
4.
At
‘Properties’
, enter the previously assigned IP address data and a subnet. The IP
address data are not accepted without subnet assignment!
5.
Transfer your project.
1
Ethernet PG/OP channel
Proceeding
VIPA System SLIO
Deployment CPU 013-CCF0R00
Hardware configuration - Ethernet PG/OP channel > Take IP address parameters in project
HB300 | CPU | 013-CCF0R00 | en | 19-30