![YASKAWA VIPA System SLIO Скачать руководство пользователя страница 58](http://html.mh-extra.com/html/yaskawa/vipa-system-slio/vipa-system-slio_manual_907132058.webp)
Order no.
013-CCF0R00
Number of DP master via CP
-
Operable function modules
64
Operable communication modules PtP
64
Operable communication modules LAN
-
Status information, alarms, diagnostics
Status display
yes
Interrupts
yes
Process alarm
yes
Diagnostic interrupt
yes
Diagnostic functions
yes, parameterizable
Diagnostics information read-out
possible
Supply voltage display
green LED
Group error display
red SF LED
Channel error display
red LED per group
Isolation
Between channels
ü
Between channels of groups to
16
Between channels and backplane bus
ü
Between channels and power supply
-
Max. potential difference between circuits
DC 75 V/ AC 50 V
Max. potential difference between inputs (Ucm)
-
Max. potential difference between Mana and Mintern
(Uiso)
-
Max. potential difference between inputs and Mana (Ucm)
-
Max. potential difference between inputs and Mintern
(Uiso)
-
Max. potential difference between Mintern and outputs
-
Insulation tested with
DC 500 V
Command processing times
Bit instructions, min.
0.02 µs
Word instruction, min.
0.02 µs
Double integer arithmetic, min.
0.02 µs
Floating-point arithmetic, min.
0.12 µs
Timers/Counters and their retentive characteristics
Number of S7 counters
512
S7 counter remanence
adjustable 0 up to 256
S7 counter remanence adjustable
C0 .. C7
VIPA System SLIO
Hardware description
Technical data
HB300 | CPU | 013-CCF0R00 | en | 19-30