* Terminal MA can be used only from DeviceNet communications. There is
no corresponding external output terminal.
• Output (Inverter
→
Master) Instance 156 (9C Hex)
Byte 1,
bit 7
Terminal
P2
Operates the Inverter’s multi-function
output terminal P2. This function is en-
abled only when Inverter constant n059
is set to 18.
0: Terminal P2 OFF
1: Terminal P2 ON
Bytes
2 and 3
Speed
Reference
Indicates the Inverter’s speed reference.
The units depend on the setting in
Inverter constant n035.
The units are not affected by the speed
scale (SS) setting.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Fault-
ed
Warn-
ing
Ready
At Ref-
erence
Reset
Rev
Run-
ning
ZSP
Run-
ning
1
Termi-
nal P2
Termi-
nal P1
Termi-
nal
MA*
---
Termi-
nal S4
Termi-
nal S3
Termi-
nal S2
Termi-
nal S1
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
4
---
5
---
6
Output Current Monitor (Low Byte)
7
Output Current Monitor (High Byte)
Data
Name
Contents