50
* 1. The status indicator is not turned ON.
* 2. Refer to the next page for input/output terminal status.
* 3. The display range is from
−
99.9 to 99.99 kW.
When regenerating, the output power will be displayed in units of
0.01 kW when
−
9.99 kW or less and in units of 0.1 kW when more
than
−
9.99 kW.
In vector control mode, “---” will be displayed.
* 4. Displayed in units of 0.1% when less than 100% and in units of 1% when
100% or more. The display range is from
−
999% to 999%.
* 5. The unit is determined by the value set for constant n035. For details,
refer to page 196.
U-61
DeviceNet consumed Connec-
tion Path (Connection Path Dur-
ing Operation)
20: Basic I/O Instance, Command
21: Extended I/O Instance, Command
100: MEMOBUS I/O Instance, Command
101: V7N Control I/O Instance, Command
102: Acceleration/Deceleration Time Control I/O In-
stance, Command
105: Extended MEMOBUS I/O Instance, Command
106: General-purpose DI/DO Control I/O Instance,
Command
U-62
MAC ID Selection (Setting on
Rotary Switches)
0 to 63
U-63
MAC ID Setting (MAC ID during
Operation)
0 to 63
U-64
Baud Rate Setting (Setting on
Rotary Switch)
0: 125 kbps
1: 250 kbps
2: 500 kbps
U-65
Baud Rate Setting (Baud Rate
during Operation)
125: 125 kbps
250: 250 kbps
500: 500 kbps
U-66
Status of DeviceNet
connection instance
1
st
digit: Status of explicit instance
0: No instance exists in the network or one is now
being prepared.
1: Waiting to be connected to the master while on-
line.
2: Waiting for the connection ID to be written in.
3: Connection completed
4: Time-out
2
nd
digit: Status of Polled ID instance
0: No instance exists in the network or one is now
being prepared.
1: Waiting to be connected to the master while on-
line.
2: Waiting for the connection ID to be written in.
3: Connection completed
4: Time-out
U-70
Frequency reference
from DeviceNet
r/
min
The frequency reference from the DeviceNet can be
monitored.
Constant
No.
Name
Unit
Description