* 3. Route the DeviceNet communications cables separately from the main
circuit wiring and other power lines.
* 4. There is a 5.5-mm scale on the front of the Inverter just above the terminal
block. Use this 5.5-mm scale to confirm the length of exposed wire when
stripping wires.
* 5. An external 24-V Power Supply is required for DeviceNet communica-
tions.
* 6. Connect terminators (121
Ω
,
±
1%, 1/4 W) to both ends of the communica-
tions line.
Open the front cover and verify that the strip length is 5.5 mm
(0.22 in.).
Wiring Inspection
After completing wiring, check the following.
• Wiring is proper.
• Wire clippings or screws are not left in the Inverter.
• Screws are securely tightened.
• Bare wires in the terminals do not contact other terminals.
If the power supply is turned ON during the FWD (or
REV) RUN command is given, the motor will start
automatically.
Turn the power supply ON after verifying that the
RUN signal is OFF.
Failure to observe this warning may result in injury.
If the FWD (or REV) RUN command is given when the RUN
command from the control circuit terminal is selected (n003
= 1), the motor will start automatically after the main circuit
input power supply is turned ON.
Scale
WARNING