![YASKAWA Varispeed V7 Скачать руководство пользователя страница 57](http://html1.mh-extra.com/html/yaskawa/varispeed-v7/varispeed-v7_instruction-manual_3554366057.webp)
56
Component Names and Settings
Rotary Switches
The rotary switches are used to set the DeviceNet baud rate and MAC
ID (node address). Always turn OFF the Inverter’s input power supply
before changing the rotary switch settings. The settings will be enabled
the next time the power is turned ON.
Baud Rate Setting Switch (S1)
MAC ID Setting Switches (S3 and S4)
The Inverter’s MAC ID is set on the MSB (S3) and LSB (S4) rotary
switches.
MAC ID = (MSB setting
×
10) + (LSB setting)
The MAC ID setting range is 0 to 63. If a value between 64 and 99 is
set, the MAC ID setting in constant n150 will be used.
Explicit Message
Communications
Up to 32 bytes of data can be transferred in
conformance with the DeviceNet AC/DC
drive profile.
Communications
Power Supply
11 to 25 VDC (20 mA max.)
Setting
0
1
2
3 to 9
Baud Rate 125 kbps
250 kbps
500 kbps
Use setting in
constant n152.
Item
Specifications
5
7
0
4
3
1 2
6
9 8
S1
S3
S4
MSB
LSB
ADDRESS
RATE
Baud rate
setting
5
7
0
4
3
1 2
6
9 8
5
7
0
4
3
1 2
6
9 8
MAC ID Setting
10 s digit (MSB)
MAC ID Setting
1 s digit (LSB)