76
* Terminal MA can be used only from DeviceNet communications. There is
no corresponding external output terminal.
• Output (Inverter
→
Master) Instance 152 (98 Hex)
Bytes
6 and 7
Decelera-
tion Time 1
Sets the Inverter’s deceleration time.
The units depend on the setting in
Inverter constant n018. (The factory set-
ting is for units of 0.1 s.) The value set
here is recorded in EEPROM. The units
are not affected by the time scale (TS)
setting.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Fault-
ed
Warn-
ing
Ready
At Ref-
erence
Reset
Rev
Run-
ning
ZSP
Run-
ning
1
---
---
Termi-
nal P2
Termi-
nal P1
Termi-
nal
MA*
Local/
Re-
mote
UV
OPE
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
4
Speed Reference (Low Byte)
5
Speed Reference (High Byte)
6
Output Current (Low Byte)
7
Output Current (High Byte)
Data
Name
Contents
Byte 0,
bit 0
Running
Indicates the Inverter’s operating status.
0: Stopped.
1: Operating forward, operating in
reverse, or applying DC injection
braking.
Data
Name
Contents