68
* These terminals can be used only from DeviceNet communications. There
are no corresponding external input terminals or output terminals.
Byte 0,
bit 5
Terminal
S6*
Inputs the function set for Inverter con-
stant n055 (Multi-function Input Selec-
tion 6.)
0: Terminal S6 function OFF
1: Terminal S6 function ON
Byte 0,
bit 6
Terminal
S7*
Inputs the function set for Inverter con-
stant n056 (Multi-function Input Selec-
tion 7.)
0: Terminal S7 function OFF
1: Terminal S7 function ON
Data
Name
Contents
Byte 1,
bit 0
External
Fault
External fault (EF0) input from communi-
cations.
0: ---
1: External fault (EF0)
Byte 1,
bit 1
Fault Reset Resets the Inverter from fault status.
0: ---
1: Reset fault.
Byte 1,
bit 5
Terminal
MA*
Operates the Inverter’s multi-function
output terminal MA. This function is en-
abled only when Inverter constant n057
is set to 18.
0: Terminal MA OFF
1: Terminal MA ON
Byte 1,
bit 6
Terminal
P1
Operates the Inverter’s multi-function
output terminal P1. This function is en-
abled only when Inverter constant n058
is set to 18.
0: Terminal P1 OFF
1: Terminal P1 ON
Data
Name
Contents