![YASKAWA Varispeed V7 Скачать руководство пользователя страница 246](http://html1.mh-extra.com/html/yaskawa/varispeed-v7/varispeed-v7_instruction-manual_3554366246.webp)
10. Specifications
245
Second Functions (Constants n050 to n079)
No.
Register
No. for
Trans-
mission
Name
Setting
Range
Setting Unit
Factory
Setting
User
Setting
Ref.
Page
050
0132
Multi-function Input Se-
lection 1 (Terminal S1)
1 to 28
1
1
159
051
0133
Multi-function Input Se-
lection 2 (Terminal S2)
1 to 28
1
2
159
052
0134
Multi-function Input Se-
lection 3 (Terminal S3)
0 to 28
1
3
159
053
0135
Multi-function Input Se-
lection 4 (Terminal S4)
1 to 28, 34
1
5
159
054
0136
Multi-function Input Se-
lection 5 (Terminal S5)
1 to 28
1
6
159
055
0137
Multi-function Input Se-
lection 6 (Terminal S6)
1 to 28
1
7
159
056
0138
Multi-function Input Se-
lection 7 (Terminal S7)
1 to 28
1
10
159
057
0139
Multi-function Output Se-
lection 1
0 to 21
1
2
164
058
013A
Multi-function Output Se-
lection 2
0 to 21
1
1
164
059
013B
Multi-function Output Se-
lection 3
0 to 21
1
0
164
064
0140
Processing During Ana-
log Frequency Refer-
ence Loss
0: Process-
ing dis-
abled
1: Process-
ing
enabled
1
0
---
068
0144
Analog Frequency Ref-
erence Gain
−
255% to
255%
1%
100%
---
069
0145
Analog Frequency Ref-
erence Bias
−
100% to
100%
1%
0%
---
070
0146
Analog Frequency Ref-
erence Filter Time Con-
stant
0.00 to
2.00 s
0.01 s
0.10 s
---
071
0147
Analog Frequency Ref-
erence Gain
−
255 to
255
1%
100%
---
072
0148
Analog Frequency Ref-
erence Bias
−
100% to
100%
1%
0%
---
073
0149
Analog Frequency Ref-
erence Filter Time Con-
stant
0.00 to
2.00 s
0.01 s
0.01 s
---
077
014D
Multi-function Analog In-
put Function
0 to 4
1
0
162
078
014E
Multi-function Analog In-
put Signal Selection
0, 1
1
0
164
079
014F
Sequence Input Double
Reading Selection
0, 1
1
0
---