![YASKAWA Varispeed V7 Скачать руководство пользователя страница 117](http://html1.mh-extra.com/html/yaskawa/varispeed-v7/varispeed-v7_instruction-manual_3554366117.webp)
116
Error Code Tables
Explicit Message Communications Errors
When there is a problem with a request message sent from the master in
explicit communications, the Inverter will return a response message
with 94 as the service code well as one of the following error codes as
the data.
Error
Code
Contents
Cause
Corrective Action
08FF
Service not
supported
The service code
is incorrect.
Correct the ser-
vice code.
09FF
Invalid
attribute value
The attribute is in-
correct.
Correct the at-
tribute.
0CFF
Object state
conflict
Attempted to
change an
Inverter constant
that cannot be
changed while the
Inverter is run-
ning.
Stop the Inverter.
0EFF
Attribute not
settable
Attempted to
change a read-
only attribute.
Correct the ser-
vice code or at-
tribute setting.
13FF
Not enough
data
The data size is
incorrect.
Correct the data
size.
14FF
Attribute not
supported
Attempted to exe-
cute a service that
is not defined for
the attribute.
Correct the ser-
vice code or at-
tribute setting.
15FF
Too much
data
The data size is
incorrect.
Correct the data
size.
16FF
Object does
not exist
An unsupported
object was speci-
fied.
Correct the class
or instance set-
ting.