6. Operating with DeviceNet Communications
99
• Object Contents
* 1. The setting ranges are the same as the ranges for the corresponding I/O
message functions.
In-
stance
At-
tribute
Name
Contents
Setting
Range
Factory Set-
ting (Hex)
Read Write
Size
00
01
Object
Soft-
ware
Revision
Indicates the As-
sembly object's
software revision.
---
0002
OK
---
Word
14
03
Data
This function is
the same as the
Basic I/O In-
stance (input).
See
note 1.
---
OK
OK
Byte x
4
15
03
Data
This function is
the same as the
Extended I/O In-
stance (input).
See
note 1.
---
OK
OK
Byte x
4
46
03
Data
This function is
the same as the
Basic I/O In-
stance (output).
---
---
OK
---
Byte x
4
47
03
Data
This function is
the same as the
Extended I/O In-
stance (output).
---
---
OK
---
Byte x
4
64
03
Data
This function is
the same as the
MEMOBUS I/O In-
stance (input).
See
note 1.
---
OK
OK
Byte x
5
65
03
Data
This function is
the same as the
V7 Standard Con-
trol I/O Instance
(input).
See
note 1.
---
OK
OK
Byte x
8
69
03
Data
This function is
the same as the
Extended
MEMOBUS I/O In-
stance (input).
See
note 1.
---
OK
OK
Byte x
8
96
03
Data
This function is
the same as the
MEMOBUS I/O In-
stance (output).
---
---
OK
---
Byte x
5
97
03
Data
This function is
the same as the
V7 Standard Con-
trol I/O Instance
(output).
---
---
OK
---
Byte x
8
9B
03
Data
This function is
the same as the
Extended
MEMOBUS I/O In-
stance (output).
---
---
OK
---
Byte x
8