Note: 1. Not initialized by constant initialization.
2. Upper limit of setting range and factory setting are doubled for 400 V
Class.
3. Depends on Inverter capacity. Refer to the next page.
4. Depends on Inverter capacity. Refer to page 152.
5. Factory setting of the model with JVOP-140 Digital Operator (with
potentiometer) is 0. Setting can be set to 1 by constant initialization.
6. The unit is determined by the value set for constant n035. For details,
refer to page 196. The unit is fixed to 0.01 Hz when inputting the fre-
quency reference using DeviceNet.
7. Depends on Inverter capacity. Refer to page 178.
8. When control mode selection (n002) is changed, factory setting corre-
sponds to the control mode. Refer to page 251.
169
01A9
Output Open-phase De-
tection Time
0 to 255 s
1 s
0 s
---
173
01AD
DC Injection Braking
Proportional Gain
1 to 999
1 = 0.001
83 (0.083)
---
174
01AE
DC Injection Braking In-
tegral Time Constant
1 to 250
1 = 4 ms
25 (100 ms)
---
175
01AF
Reducing Carrier Fre-
quency Selection At Low
Speed
0, 1
1
0
154
176
01B0
Constant Copy Function
Selection
rdy, rEd,
Cpy, vFy,
vA, Sno
rdy
186
177
01B1
Constant Read Selection
Prohibit
0, 1
1
0
187
178
01B2
Fault History
Stores, dis-
plays most
recent 4
alarms
Setting dis-
abled
-
52
179
01B3
Software Version No.
Displays
lower-
place 4
digits of
software
No.
Setting dis-
abled
-
49
No.
Register
No. for
Trans-
mission
Name
Setting
Range
Setting Unit
Factory
Setting
User
Setting
Ref.
Page