![YASKAWA Varispeed V7 Скачать руководство пользователя страница 66](http://html1.mh-extra.com/html/yaskawa/varispeed-v7/varispeed-v7_instruction-manual_3554366066.webp)
6. Operating with DeviceNet Communications
65
• Input (Master
→
Inverter) Instance 100 (64 Hex)
• Output (Inverter
→
Master) Instance 150 (96 Hex)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Function Code
1
Register Number (High Byte)
2
Register Number (Low Byte)
3
Register Data (High Byte)
4
Register Data (Low Byte)
Data
Name
Contents
Byte 0
Function
Code
Set the MEMOBUS (command mes-
sage) function code.
03 Hex: Read
10 Hex: Write
00 Hex: Do not execute.
Bytes
1 and 2
Register
Number
Set the Inverter’s MEMOBUS register
number.
Bytes
3 and 4
Register
Data
Set the write data when executing a ME-
MOBUS WRITE command.
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Function Code
1
Register Number (High Byte)
2
Register Number (Low Byte)
3
Register Data (High Byte)
4
Register Data (Low Byte)