SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
4.10 Test Run Checklist
4.10 Test Run Checklist
Review the checklist before performing a test run. Check each item that applies.
Check the items that correspond to the control mode being used.
WARNING!
Ensure start/stop and safety circuits are wired properly and in the correct state before energizing the drive. Failure to
comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary closure on
terminal S1 may cause the drive to start.
Proceed to the following checklist after checking items 4 through 9.
No.
Checklist
Page
1
Thoroughly read the manual before performing a test run.
—
2
Turn the power on.
3
Set the voltage for the power supply to E1-01.
No.
Checklist
Page
V/f Control (A1-02 = 0)
4
Perform Auto-Tuning for Energy Savings if using Energy Saving functions.
Open Loop Vector Control (A1-02 = 2)
5
Uncouple the load from the motor when performing Rotational Auto-Tuning.
6
Perform Rotational Auto-Tuning.
7
The following data entered during Auto-Tuning should match the information written on the motor nameplate:
• motor rated output power (kW)
→
T1-02
• rated voltage (V)
→
T1-03
• rated current (A)
→
T1-04
• base frequency (Hz)
→
T1-05
• number of motor poles
→
T1-06
• motor rotations per minutes (r/min)
→
T1-07
PM Open Loop Vector Control (A1-02 = 5)
8
Set permanent motor parameters E5-01 through E5-24
No.
Checklist
Page
9
The
should illuminate after giving a run command.
—
10
To give a run command and frequency reference from the LED Digital Operator, press
to set to
LOCAL. The LO/RE key lights while LOCAL is displayed.
11
If the motor rotates in the opposite direction during the test run, switch two of the drive output terminals (U/
T1, V/T2, W/T3).
12
Select the correct duty rating (C6-01) for the application.
—
13
Set the correct values for the motor rated current (E2-01) and the motor protection selection (L1-01) to ensure
motor thermal protection.
—
14
If the run command and frequency reference are provided via the control circuit terminals, set the drive for
REMOTE and be sure the LO/RE light is out.
15
If the control circuit terminals should supply the frequency reference, select the correct voltage input signal
level (0 to 10 V) or the correct current input signal level (4 to 20 mA or 0 to 20 mA).
16
Set the proper voltage to terminal A1 and/or A2. (0 to 10 V).
17
Set the proper current to terminal A2. (4 to 20 mA or 0 to 20 mA).
18
When current input is used, set H3-09 to “2” (4 to 20 mA) or “3” (0 to 20 mA) and set H3-10 to “0”.
—
19
When current input is used, switch the drive built-in DIP switch S1 from the V-side (OFF) to I-side (ON).
—
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...