6.6 Operator Programming Errors
264
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Cause
Possible Solutions
While an input terminal was set to switch between external reference 1
and 2 (H1-
= 2), one of the following contradictory setting was also
present:
• The pulse train input was set for frequency reference 2 (b1-15 = 4)
while the pulse train input was not assigned to act as the frequency
reference (H6-01)
≠
0).
• An option card is not connected, although the frequency reference and
Run command are assigned to be given from an option card (b1-15 = 3
and b1-16 = 3).
• Though frequency reference 2 is set to be given from an analog input
(b1-15 = 1), an analog input terminal has not been assigned to the speed
reference (H3-02 or H3-10 = 0).
• Though the drive is not set for Simple PG feedback in V/f Control
(H6-01 = 3), an input terminal is assigned for FWD/REV detection
with Simple PG (H1-
= 7E).
• Check the input terminal settings for any contradictory functions.
• Correct settings for multi-function input terminals.
LED Operator Display
Error Name
oPE04
Initialization required.
Cause
Possible Solutions
The drive, control board, or terminal board has been replaced and the
parameter settings between the control board and the terminal board no
longer match.
To load the parameter settings to the drive that are stored in the terminal
board, set A1-03 to 5550. Initialize parameters after drive replacement
by setting A1-03 to 1110 or 2220.
LED Operator Display
Error Name
oPE05
Run Command/Frequency Reference Source Selection Error
Cause
Possible Solutions
Frequency reference is assigned to an option card (b1-01 = 3) that is not
connected to the drive.
Reconnect the option card to the drive.
The Run command is assigned to an option card (b1-02 = 3) that is not
connected to the drive.
Frequency reference is assigned to the pulse train input (b1-01 = 4), but
terminal RP is not set for pulse train input (H6-01 > 0)
Set H6-01 to “0”.
LED Operator Display
Error Name
oPE07
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs
H3-02 through to H3-10 and PID functions conflict.
Cause
Possible Solutions
H3-02 and H3-10 are set to the same value.
Change the settings to H3-02 and H3-10 so that functions no longer
conflict.
Note:
Both 0 (primary analog frequency reference) and F (Not
Used) can be set to H3-02 and H3-10 at the same time.
The following simultaneous contradictory settings: H3-02 or H3-10 = B
(PID Feedback) H6-01 (Pulse Train Input) = 1 (PID Feedback)
Disable one of the PID selections.
The following simultaneous contradictory settings: H3-02 or H3-10 = C
(PID Target Value) H6-01 = 2 (pulse train input sets the PID target value)
The following simultaneous contradictory settings: H3-02 or H3-10 = C
(PID Target Value) b5-18 = 1 (enables b5-19 as the target PID value)
The following simultaneous contradictory settings: H6-01 or H3-10 = C
(PID Target Value) b5-18 = 1 (enables b5-19 as the target PID value)
LED Operator Display
Error Name
oPE08
Parameter Selection Error
A function has been set that cannot be used in the motor control method
selected.
Cause
Possible Solutions
Attempted to use a function available only in Open Loop Vector Control,
though the drive is set for V/f Control.
Check the motor control method and the functions available.
Simple V/f with PG was enabled while not in V/f Control (H6-01 = 3).
To use Simple V/f with PG, ensure the motor control method has been
set to V/f Control (A1-02 = “0”).
In Open Loop Vector Control, n2-02 is greater than n2-03
Correct parameter settings so that n2-02 is less than n2-03.
In Open Loop Vector Control, C4-02 is greater than C4-06
Correct parameter settings so that C4-02 is less than C4-06.
The Disturb waveform function can only be used when running V/f
Control.
If using the Disturb function, make sure the drive is set for V/f Control
(A1-02 = 0).
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...