B.3 Parameter Table
356
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
S4-06
KEB End Voltage
Sets the DC bus voltage level at that the drive assumes
the power supply has returned. If this level is exceeded
for longer than S4-07 the drive starts reaccelerating to
the set frequency reference. The setting value depends
on the selection in parameter S4-02.
0.0 to
200.0
200.0%
A
A
A
6B5
S4-07
KEB End Detection
Time
Sets the time for that the DC bus voltage must exceed
the level set in S4-06 in order to end the KEB function
and reaccelerate to the set frequency reference.
0 to 2000
0 ms
A
A
A
6B6
S4-08
KEB 1 Phase Loss
Detection Level
Defines the DC bus voltage ripple that indicates a one
phase loss, thus triggering the KEB function.
0 to 400
0 V
A
A
A
6B7
S4-09
KEB 1 Phase Loss
Sampling Time
Sets the sampling time used to detect one input phase
loss.
0 to 3000
0 ms
A
A
A
6B8
S4-10
KEB 1 Phase Loss
Detection Time
Sets the time that the ripple in the DC bus voltage must
exceed the level set in S4-08 to trigger one phase loss
detection.
0 to 10
10 ms
A
A
A
6B9
S4-11
KEB Target Voltage
When KEB 1 or KEB 3 is selected and S4-02 is set to 0,
the drive attempts to keep the DC bus voltage at the
traget voltage defined in S4-11 multiplied by E1-01.
0.80 to
1.50
1.35
A
A
A
6BA
S4-12
KEB Hold Time
Once KEB is complete, S4-12 sets the time to hold the
frequency reference before reacceleration.
0.0 to 10.0
0.0 s
A
A
A
6BB
S4-13
KEB Minimum
Operation Time
Sets the minimum operation time for KEB once it is
triggered.
0 to 2000
50 ms
A
A
A
6BC
S4-14
KEB Reacceleration
Prohibit Frequency
Sets the frequency level to prohibit re-acceleration after
the power returned. If the drive output frequency fell
below S4-14 during KEB operation the drive will
decelerate the motor to stop, even if the power returns.
0.0 to
100.0
0.0%
A
A
A
6BD
S5: KEB Accel/Decel Settings
S5 parameters govern acceleration and deceleration when performing KEB 1 and KEB 2.
S5-01
KEB Decel Time 1
Sets decel time 1 for the start of KEB. S5-01 is enabled
when the output frequency is greater than S5-03.
0.0 to
200.0
0.0 s
A
A
A
6C0
S5-02
KEB Decel Time 2
Sets decel time 2 for the start of KEB. S5-02 is enabled
when the output frequency is less than or equal to S5-03.
0.0 to
200.0
0.0 s
A
A
A
6C1
S5-03
KEB Decel Time
Switching Frequency
Sets the frequency for KEB to switch between KEB
decel time 1 and KEB decel time 2.
0.0 to
100.0
0.0%
A
A
A
6C2
S5-04
KEB Decel Time
Switching Time
Sets the time constant used to switch over from
deceleration time 1 to deceleration time 2 during KEB.
0.0 to 10.0
0.0 s
A
A
A
6C3
S5-05
KEB Synchronous
Acceleration Time
Sets time to accelerate from the frequency after KEB to
the set frequency reference. This setting can be used to
let multiple drives accelerate synchronously back to the
set speed after power loss.
0.0 to
200.0
0.0 s
A
A
A
6C4
S5-06
S-Curve at KEB
Deceleration Start
Sets the S-curve time when KEB begins decelerating the
drive.
0.00 to
2.50
0.20 s
A
A
A
6C5
S5-07
Frequency Gain at KEB
Start during Constant
Speed
Sets the output frequency reduction step applied when
power loss is detected during constant speed operation
and then KEB starts. Percent of frequency reduction =
(slip frequency just before KEB)
×
S5-07
×
2
0 to 300
100%
A
A
A
6C6
S5-08
Frequency Gain at KEB
Start during
Acceleration
Sets the output frequency reduction step applied when
power loss is detected during acceleration and then KEB
starts. Percent of frequency reduction = (slip frequency
just before KEB)
×
S5-08
×
2
0 to 300
100%
A
A
A
6C7
S5-09
Frequency Gain at KEB
Start during
Deceleration
Sets the output frequency reduction step applied when
power loss is detected during deceleration and then
KEB starts. Percent of frequency reduction = (slip
frequency just before KEB)
×
S5-09
×
2
0 to 300
100%
A
A
A
6C8
S5-10
Synchronous
Deceleration ov
Prevention
Enables or disables overvoltage prevention during
synchronous KEB operation (S4-01 = 2).
0: Disabled (requires a braking option)
1: Enabled
0, 1
0
A
A
A
6C9
No.
Name
Description
Range
Def.
Control
Mode
Addr
. Hex
Pg.
V/f OL
V
PM
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...