314
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
A.6 Drive Derating Data
A.6 Drive Derating Data
Derating allows the drive to operate in conditions above the rated specifications, such as ambient temperature, altitude,
and default carrier frequency. Derating a drive with a rated output current of 10 A down to 8 A, for example, makes it
possible to run the same drive continuously at hotter temperatures.
◆
Carrier Frequency Derating
As the carrier frequency of the drive is increased above the factory setting the drive capacity should be derated according
to
Figure A.1
Figure A.1 Carrier Frequency Derating
◆
Temperature Derating
As the ambient temperature for the drive is increased above the drive specification the drive should be derated.
Additionally parameter L8-35 Installation Method Selection on page
should be set according to enclosure type and
mounting method as illustrated in
■
Output Current Derating Due to Ambient Temperature
If the ambient temperature is above the drive specification or if drives are side-by-side mounted in a cabinet, the
parameters L8-12 and L8-35 must be set according to the installation conditions. The output current is derated as shown
in
No.
Name
Description
Range
Def.
L8-12
Ambient
Temperature Setting
Adjust the drive overload (oL2) protection level when the drive is
installed in an environment that exceeds its ambient temperature rating.
40 to 60
40 °C
L8-35
Installation Method
Selection
0: Heatsink-Cooled Drive
1: Side-by-Side Mounting
2: NEMA Type 1 Drive
3: Finless Drive or External Heatsink Installation
0 to 3
0
Installation Type
<1> To use finless drive or external heatsink installation between –10 to 50
°
C without current derating,
Set L8-35 to 0
Ensure airflow of 0.5 m/s around the drive
Temperature Derating
Heatsink-Cooled Drive
–10 to 50
°
C = 100%
NEMA Type 1 Drive
–10 to 40
°
C = 100%. Derating from 100% at 40
°
C to 85% at 50
°
C.
Side-by-Side Mounting
–10 to 30
°
C = 100%. Derating from 100% at 30
°
C to 70% at 50
°
C.
Finless Drive or External Heatsink Installation
–10 to 35
°
C = 100%. Derating from 100% at 35
°
C to 80% at 50
°
C.
ND
10 (8)
15
0
HD
2
ND
10 (8)
15
0
HD
2
200 V Class:
80% of HD
400 V Class:
60% of HD
Carrier Frequency Derating
Drive Rated
Current
Carrier Frequency Selection (C6-02)
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...