B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
331
Pa
ra
met
er
Li
st
B
E2-09
Motor Mechanical
Loss
Sets the motor mechanical loss as a percentage of motor
rated power (kW). Adjust in the following circumstances:
When there is a large amount of torque loss due to motor
bearing friction.
When there is a large amount of torque loss.
0.0 to 10.0
0.0%
−
A
−
316
E2-10
Motor Iron Loss
for Torque
Compensation
Sets the motor iron loss in watts (W).
0 to 65535
A
−
−
317
E2-11
Motor Rated Power
Sets the motor rated power in kilowatts (kW).
Automatically set during Auto-Tuning. (1 HP = 0.746
kW).
0.00 to
650.00
S
S
−
318
E2-12
Motor Iron-Core
Saturation
Coefficient 3
Set to the motor iron saturation coefficient at 130% of
magnetic flux.
Automatically set during rotational Auto-Tuning.
1.30 to 5.00
1.30
−
A
−
328
E3: V/f Characteristics for Motor 2
Use E3 parameters to set the V/f pattern for a second motor.
E3-01
Motor 2 Control
Mode Selection
0: V/f Control
2: Open Loop Vector (OLV)
Motor 2 cannot be a PM motor. Motor overload (oL1)
protection for motor 2 is set using parameter L1-01.
0 or 2
0
A
A
−
319
E3-04
Motor 2 Max
Output Frequency
These parameters set the V/f pattern for motor 2.
To set linear V/f characteristics, set the same values for
E3-07 and E3-09. In this case, the setting for E3-08 will be
disregarded. Ensure that the four frequencies are set
according to these rules or oPE10 fault will occur:
E3-04
≥
E3-06 > E3-07 > E3-09
40.0 to
400.0
50.0 Hz
A
A
−
31A
E3-05
Motor 2 Max
Voltage
0.0 to 255.0
200.0 V
A
A
−
31B
E3-06
Motor 2 Base
Frequency
0.0 to
[E3-04]
50.0 Hz
A
A
−
31C
E3-07
Motor 2 Mid
Output Frequency
0.0 to
[E3-04]
2.5 Hz
A
A
−
31D
E3-08
Motor 2 Mid
Output Frequency
Voltage
0.0 to 255.0
16.0 V
A
A
−
31E
E3-09
Motor 2 Minimum
Output Frequency
0.0 to
[E3-04]
1.3 Hz
A
A
−
31F
E3-10
Motor 2 Minimum
Output Frequency
Voltage
0.0 to 255.0
12.0 V
A
A
−
320
E3-11
Motor 2 Mid
Output Frequency
2
0.0 to
[E3-04]
0.0 Hz
A
A
−
345
E3-12
Motor 2 Mid
Output Frequency
Voltage 2
0.0 to 255.0
0.0 V
A
A
−
346
E3-13
Motor 2 Base
Voltage
0.0 to 255.0
0.0 V
A
S
−
347
E4: Motor 2 Parameters
Use E4 parameters to control a second motor operating on the same drive.
E4-01
Motor 2 Rated
Current
Sets the motor 2 nameplate full load current in amperes
(A). This value is automatically set during Auto-Tuning.
10 to 200%
of drive
rated
current
A
A
−
321
E4-02
Motor 2 Rated Slip
Sets the motor 2 rated slip in Hz. Automatically set
during Auto-Tuning.
0.00 to
20.00
A
A
−
322
E4-03
Motor 2 Rated No-
Load Current
Sets the magnetizing current of motor 2 in Ampere.
Automatically set during Rotational Auto-Tuning.
0 to
[E4-01]
A
A
−
323
E4-04
Motor 2 Motor
Poles
Sets the number of poles of motor 2. This value is
automatically set during Auto-Tuning.
2 to 48
4 poles
A
A
−
324
No.
Name
Description
Range
Def.
Control
Mode
Addr. Hex Pg.
V/f OL
V PM
E3-09 E3-07 E3-06 E3-11 E3-04
E3-05
E3-12
E3-13
E3-08
E3-10
VACrms Out (V)
Frequency (Hz)
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...