B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
335
Pa
ra
met
er
Li
st
B
F6-35
CANopen Node ID
Selection
Sets the Node ID for a CANopen.
0 to 127
A A A
3D0
–
F6-36
CANopen Communication
Speed
0: Auto-adjust
1: 10 kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
0 to 8
A A A
3D1
–
F6-50
DeviceNet MAC Address
Selects the drives MAC address for DeviceNet.
0 to 64
0
A A A
3C1
–
F6-51
Device Net
Communications Speed
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Adjustable from Network
4: Detect automatically
0 to 4
0
A A A
3C2
–
F6-52
DeviceNet PCA Setting
I/O Polled Consuming Assembly Data Instance
0 to 255
21
A A A
3C3
–
F6-53
DeviceNet PPA Setting
I/O Polled Producing Assembly Data Instance
0 to 255
71
A A A
3C4
–
F6-54
DeviceNet Idle Mode Fault
Detection
Selects if a EF0 fault is detected when no data are received
from the master.
0: Detection enabled
1: No detection
0 or 1
0
A A A
3C5
–
F6-55
DeviceNet Baud Rate
Monitor
Used to verify the baud rate running on the network.
0: 125 kbps
1: 250 kbps
2: 500 kbps
0 to 2
0
A A A
3C6
–
F6-56
DeviceNet Speed Scaling
Sets the scaling factor for the speed monitor in DeviceNet
Class ID 2AH Object.
-15 to 15
0
A A A
3D7
–
F6-57
DeviceNet Current Scaling
Sets the scaling factor for the output current monitor in
DeviceNet Class ID 2AH Object.
-15 to 15
0
A A A
3D8
–
F6-58
DeviceNet Torque Scaling
Sets the scaling factor for the torque monitor in DeviceNet
Class ID 2AH Object.
-15 to 15
0
A A A
3D9
–
F6-59
DeviceNet Power Scaling
Sets the scaling factor for the power monitor in DeviceNet
Class ID 2AH Object.
-15 to 15
0
A A A
3DA
–
F6-60
DeviceNet Voltage Scaling
Sets the scaling factor for the voltage monitor in DeviceNet
Class ID 2AH Object.
-15 to 15
0
A A A
3DB
–
F6-61
DeviceNet Time Scaling
Sets the scaling factor for the time monitor in DeviceNet
Class ID 2AH Object.
-15 to 15
0
A A A
3DC
–
F6-62
DeviceNet Heartbeat
Interval
Sets the heartbeat interval for DeviceNet communications.
0 to 10
0
A A A
3DD
–
F6-63
DeviceNet Network MAC
ID
Used to verify the MAC ID the drive has been assigned.
0 to 63
0
A A A
3DE
–
F6-64 to
F6-69
Dynamic Assembly
Parameters (Reserved)
Reserved for Dynamic I/O Assembly Parameters.
0 to
FFFFH
0
A A A
3DF to
3E4
–
F6-70 to
F6-71
3C7,
3C8
–
<18> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.
<35> Setting range varies by the software version the drive is running.
Software versions 6002 or later: 0 to 126
Software versions 6001 or earlier: 0 to 127
<36> Default setting is determined by the initialize mode the drive is set for (o2-09).
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f OL
V
P
M
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...