5.5 E: Motor Parameters
154
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
explains the motor code setting.
Figure 5.35
Figure 5.35 PM Motor Code
■
E5-02: Motor Rated Power (PM OLV)
Sets the rated power of the motor.
Note:
This parameter is not reset when the drive is initialized using A1-03.
■
E5-03: Motor Rated Current (PM OLV)
Sets the motor rated current in amps.
Note: 1.
Setting units vary by the maximum allowable motor capacity, which is determined by C6-01 and o2-04. Drives up to 11 kW display a
two-digit value, while drives 11 kW and larger display a single-digit value.
2.
This parameter is not reset when the drive is initialized using A1-03.
■
E5-04: Number of Motor Poles (PM OLV)
Sets the number of motor poles.
Note:
This parameter is not reset when the drive is initialized using A1-03.
■
E5-05: Motor Stator Resistance (PM OLV)
Set the resistance for each motor phase (not line-to-line resistance). When measuring the resistance manually make sure
to enter the resistance of one phase into E5-05.
Note:
This parameter is not reset when the drive is initialized using A1-03.
■
E5-06: Motor d-Axis Inductance (PM OLV)
Sets the d axis inductance in units of 0.01 mH.
Note:
This parameter is not reset when the drive is initialized using A1-03.
No.
Parameter Name
Setting Range
Default
E5-02
Motor Rated Power
0.10 to 18.50 kW
Determined by
E5-01
No.
Parameter Name
Setting Range
Default
E5-03
Motor Rated Current
10 to 200% of drive rated
current
Determined by
E5-01
No.
Parameter Name
Setting Range
Default
E5-04
Number of Motor Poles
2 to 48
Determined by
E5-01
No.
Parameter Name
Setting Range
Default
E5-05
Motor Stator Resistance
0.000 to 65.000
Ω
Determined by
E5-01
No.
Parameter Name
Setting Range
Default
E5-06
Motor d-Axis Inductance
0.00 to 300.00 mH
Determined by
E5-01
0 0 0 0
0: 1800 r/min Series
1: 3600 r/min Series
2: 1750 r/min Series
3: 1450 r/min Series
4: 1150 r/min Series
F: Special Motor
Motor Voltage Class
and Capacity
0: Pico Motor
(SMRA Series)
1: Derated Torque for IPM
Motors
(SSR 1 Series)
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...