310
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
A.3 Three-Phase 400 V Class Drives
A.3 Three-Phase 400 V Class Drives
Table A.3 Power Ratings
Note:
Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated input and output
current, overload capacity, carrier frequency and current limit. Set parameter C6-01 to “0” (default) for HD or “1” for ND.
Item
Specification
CIMR-TC4V
0001 0002 0004 0005 0007 0009 0011 0018 0023 0031 0038
Maximum Applicable Motor Capacity
<1> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor rated current.
HD Rating
0.2
0.4
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11.0
15.0
ND Rating
0.4
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11.0
15.0
18.5
Input
Input Current (A)
<2> Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and power supply impedance.
HD Rating
1.2
1.8
3.2
4.4
6.0
8.2
10.4
15.0
20.0
29.0
39.0
ND Rating
1.2
2.1
4.3
5.9
8.1
9.4 14.0
20.0
24.0
38.0
44.0
Output
Output Current (kVA)
<3> Rated motor capacity is calculated with a rated output voltage of 440 V.
<4> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
0.9
1.4
2.6
3.7
4.2
5.5
7.0
11.3
13.7
18.3
23.6
ND Rating
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
0.9
1.6
3.1
4.1
5.3
6.7 8.5
13.3
17.5
23.6
29.0
Output Current (A)
1.2
1.8
3.4
4.8
5.5
7.2
9.2
14.8
18.0
24.0
31.0
ND Rating
1.2
2.1
4.1
5.4
6.9
8.8 11.1
17.5
23.0
31.0
38.0
Overload Tolerance
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
User adjustable between 2 and 15 kHz (see HD output current line of this table
for default values)
Maximum Output Voltage (V)
Three-phase: 380 to 480 V (proportional to input voltage)
Maximum Output Frequency (Hz)
400 Hz (user-adjustable)
Power
Supply
Rated Voltage Rated Frequency
Three-phase: 380 to 480 V 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Harmonic Corrective Actions
DC Reactor
Optional
Total Loss (W)
HD Rating
30.6 43.8
60.2 96.9 111.7 117.5 148.7 227.7 282.1 369.0 434.5
ND Rating
19.6
32.4
47.3
66.3
87.0
95.1 127.7 259.6 315.2 426.9 458.0
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...