Guarding Against Harmful Materials
When installing IP20/IP00 drives, use an enclosure that prevents foreign material from entering the drive from above or
below.
■
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of
grounded systems, contact your dealer or Yaskawa for instructions.
◆
EMC Guidelines Compliance
This drive is tested according to European standards EN61800-3 and it complies with the EMC guidelines.
■
EMC Filter Installation
The following conditions must be met to ensure continued compliance with guidelines.
for EMC filter selection.
Installation Method
Verify the following installation conditions to ensure that other devices and machinery used in combination with this
drive also comply with EMC guidelines.
1.
Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards.
2.
Place the drive and EMC noise filter in the same enclosure.
3.
Use braided shield cable for the drive and motor wiring or run the wiring through a metal conduit.
4.
Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
Figure D.2
Figure D.2 Installation Method
Three-Phase 400 V Class
4V0001
A6T3
3
FWH-40B
40
4V0002
A6T6
6
FWH-40B
40
4V0004
A6T15
15
FWH-50B
50
4V0005
A6T20
20
FWH-70B
70
4V0007
A6T25
25
FWH-70B
70
4V0009
A6T25
25
FWH-90B
90
4V0011
A6T30
30
FWH-90B
90
4V0018
Not Available
FWH-80B
80
4V0023
FWH-100B
100
4V0031
FWH-125B
125
4V0038
FWH-200B
200
A – Drive
D – Metal conduit
B – 20 m max cable length between drive and motor
E – Ground wire should be as short as possible.
C – Motor
Drive Model CIMR-T
Non-Time Delay Class-T
Fuse Type
(Manufacturer: Ferraz)
600 Vac, 200 kAIR
Fuse Ampere Rating
(A)
Fuse Type
(Manufacturer: Bussmann)
500 Vac, 200 kAIR
Fuse Ampere Rating
(A)
A
B
D
E
C
M
U/T1
V/T2
W/T3
U
V
W
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...