B.3 Parameter Table
334
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
F1-08
Overspeed Detection Level
Sets the speed feedback level which has to be exceeded for
the time set in F1-09 before an OS fault will occur.
Set as a percentage of the maximum output frequency (E1-
04).
0 to 120 115% A
− −
387
F1-09
Overspeed Detection Delay
Time
Sets the time in seconds for which the speed feedback has
to exceed the overspeed detection level F1-08 before an OS
fault will occur.
0.0 to 2.0
1.0
A
− −
388
F1-10
Excessive Speed Deviation
Detection Level
Sets the allowable deviation between motor speed and
frequency reference before a speed deviation fault (DEv) is
triggered.
Set as a percentage of the maximum output frequency (E1-
04).
0 to 50
10% A
− −
389
F1-11
Excessive Speed Deviation
Detection Delay Time
Sets the time in seconds for which a deviation between
motor speed and frequency reference has to exceed the
speed deviation detection level F1-10 before a DEV fault
will occur.
0.0 to
10.0
0.5 s A
− −
38A
F1-14
PG Open-Circuit Detection
Time
Sets the time for which no PG pulses must be detected
before a PG Open (PGO) fault is triggered.
0.0 to
10.0
2.0 s A
− −
38D
F6: Communication Option Card
Use F6 parameters to program the drive for serial communication.
F6-01
Communications Error
operation Selection
Selects the operation after a communications error
occurred.
0: Ramp to stop using current accel/decel time
1: Coast to stop
2: Fast-stop using C1-09
3: Alarm only
0 to 3
1
A A A
3A2
F6-02
External Fault from Comm.
Option Detection Selection
Sets when an external fault from a comm option is
detected.
0: Always detected
1: Detection during Run only
0 or 1
0
A A A
3A3
F6-03
External Fault from Comm.
Option Operation Selection
Selects the operation after an external fault set by a
communications option (EF0).
0: Ramp to stop using current accel/decel time
1: Coast to stop
2: Fast-stop using C1-09
3: Alarm only
0 to 3
1
A A A
3A4
F6-07
NetRef/ComRef Function
Preselection Capability
0: Multi-step reference disabled (same as F7)
1: Multi-step reference enabled (same as V7)
0, 1
1
A A A
3A8
F6-08
Comm. Parameter Reset
0: Communication-related parameters (F6-
) are not
reset when the drive is initialized using A1-03.
1: Reset all communication-related parameters (F6-
)
when the drive is initialized using A1-03.
0 to 1
0
A A A
36A
F6-10
CC-Link Node Address
Sets the node address if a CC-Link is installed.
0 to 64
0
A A A
3E6
–
F6-11
CC-Link Communication
Speed
0: 156 kbps
1: 625 kbps
2: 2.5 kbps
3: 5 Mbps
4: 10 Mbps
0 to 4
0
A A A
3E7
–
F6-14
bUS Error Auto Reset
Selects if a BUS fault can be automatically reset.
0: Disabled
1: Enabled
0 or 1
0
A A A
3BB
–
F6-30
PROFIBUS-DP Node
Address
Sets the node address for a PROFIBUS.
0 to 125
0
A A A
3CB
–
F6-31
PROFIBUS-DP Clear Mode
Selection
Selects the operation when a "Clear Mode" command is
received.
0: Resets drive operation.
1: Maintains the previous operation state.
0 or 1
0
A A A
3CC
–
F6-32
PROFIBUS-DP Data
Format Selection
0: PPO Type
1: Conventional
0 or 1
0
A A A
3CD
–
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f OL
V
P
M
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...