5.8 L: Protection Functions
188
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
The PTC must have the following characteristics for one motor phase. Normally a motor is protected by three PTCs
connected in series.
Figure 5.67
Figure 5.67 Motor PTC Characteristics
Overheat detection using a PTC can be set up by parameters L1-03, L1-04, and L1-05 as explained below.
■
L1-03: Motor Overheat Alarm Operation Selection (PTC input)
Determines what action the drive should take when the PTC input signal reaches the motor overheat alarm level (PTC
input level: Tr-5
°C
).
Setting 0: Ramp to Stop
The drive stops the motor using the active deceleration time.
Setting 1: Coast to Stop
The drive output is switched off and the motor coasts to stop.
Setting 2: Fast-stop
The drive stops the motor using the Fast-stop time set in parameter C1-09.
Setting 3: Alarm Only
The operation is continued and an oH3 alarm is displayed on the digital operator.
■
L1-04: Motor Overheat Fault Operation Selection (PTC input)
Determines what action the drive should take when the PTC input signal reaches the motor overheat fault level (PTC
input level: Tr-5
°C
).
Setting 0: Ramp to Stop
The drive stops the motor using the active deceleration time.
Setting 1: Coast to Stop
The drive output is switched off and the motor coasts to stop.
Setting 2: Fast-stop
The drive stops the motor using the Fast-stop time set in parameter C1-09.
■
L1-05: Motor Temperature Input Filter Time (PTC input)
Used to set a filter on the PTC signal in order to prevent a motor overheat fault from being mistakenly detected.
No.
Name
Setting Range
Default
L1-03
Motor Overheat Alarm Operation Selection (PTC input)
0 to 3
3
No.
Name
Setting Range
Default
L1-04
Motor Overheat Fault Operation Selection (PTC input)
0 to 2
1
No.
Name
Setting Range
Default
L1-05
Motor Temperature Input Filter Time (PTC input)
0.00 to 10.00 s
0.20 s
Tr’
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...