D.2 European Standards
414
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
■
EMC Filters
The drive should be installed with the EMC filters listed below in order to comply with the EN 61800-3, category C1
requirements.
Note:
If the Safe Disable function of the drive is part of the safety concept of a machine or installation and used for a safe stop
according to EN60204-1, stop category 0, use only filters manufactured by Schaffner as listed below.
Table D.2 EN 61800-3 Category C1 Filters
Note:
EMC filters for models CIMR-TC2V0030 through 0069 are in compliance with IEC61800–3, Category 2. All other models
comply with Category 1.
Drive
CIMR-TC
Filter Data (Manufacturer: Schaffner)
Type
Rated
Current
(A)
Weight
(kg)
Dimensions
[W x L x H]
(mm)
Dimensions
Y x X
Drive
Mounting
Screw A
Filter
Mounting
Screw
200 V Single-Phase Units
BV0001
FS23638-10-07
10
0.44
71 x 169 x 45
51 x 156
M4
M5
BV0002
FS23638-10-07
10
0.44
71 x 169 x 45
51 x 156
M4
M5
BV0003
FS23638-10-07
10
0.44
71 x 169 x 45
51 x 156
M4
M5
BV0006
FS23638-20-07
20
0.75
111 x 169 x 50
91 x 156
M4
M5
BV0010
FS23638-20-07
20
0.75
111 x 169 x 50
91 x 156
M4
M5
BV0012
FS23638-30-07
30
1.1
144 x 174 x 50
120 x 161
M4
M5
200 V Three-Phase Units
2V0001
FS23637-8-07
7.3
0.4
71 x 169 x 40
51 x 156
M4
M5
2V0002
FS23637-8-07
7.3
0.4
71 x 169 x 40
51 x 156
M4
M5
2V0004
FS23637-8-07
7.3
0.4
71 x 169 x 40
51 x 156
M4
M5
2V0006
FS23637-8-07
7.3
0.4
71 x 169 x 40
51 x 156
M4
M5
2V0010
FS23637-14-07
14
0.6
111 x 169 x 45
91 x 156
M4
M5
2V0012
FS23637-14-07
14
0.6
111 x 169 x 45
91 x 156
M4
M5
2V0020
FS23637-24-07
24
0.9
144 x 174 x 50
120 x 161
M4
M5
2V0030
FS23637-52-07
52
2.0
137 x 304 x 56
100 x 289
M5
M5
2V0040
FS23637-52-07
52
2.0
137 x 304 x 56
100 x 289
M5
M5
2V0056
FS23637-68-07
68
2.6
175 x 340 x 65
130 x 325
M5
M6
2V0069
FS23637-80-07
80
3.1
212 x 393 x 65
167 x 378
M6
M8
400 V Three-Phase Units
4V0001
FS23639-5-07
5
0.5
111 x 169 x 45
91 x 156
M4
M5
4V0002
FS23639-5-07
5
0.5
111 x 169 x 45
91 x 156
M4
M5
4V0004
FS23639-5-07
5
0.5
111 x 169 x 45
91 x 156
M4
M5
4V0005
FS23639-10-07
10
0.7
111 x 169 x 45
91 x 156
M4
M5
4V0007
FS23639-10-07
10
0.7
111 x 169 x 45
91 x 156
M4
M5
4V0009
FS23639-10-07
10
0.7
111 x 169 x 45
91 x 156
M4
M5
4V0011
FS23639-15-07
15
0.9
144 x 174 x 50
120 x 161
M4
M5
4V0018
FS23639-30-07
30
1.8
137 x 304 x 56
100 x 289
M5
M5
4V0023
FS23639-30-07
30
1.8
137 x 304 x 56
100 x 289
M5
M5
4V0031
FS23639-50-07
50
2.7
175 x 340 x 65
130 x 325
M5
M6
4V0038
FS23639-50-07
50
2.7
175 x 340 x 65
130 x 325
M5
M6
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...