B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
355
Pa
ra
met
er
Li
st
B
◆
S: Functions for Textile Applications
The S parameters are designed specifically for textile applications. They set and adjust the Disturb function, gain levels
for the frequency reference, braking transistor characteristics, and various aspects of KEB.
No.
Name
Description
Range
Def.
Control
Mode
Addr
. Hex
Pg.
V/f OL
V
PM
S1: Disturb Function
Various aspects of the Disturb function are determined by the S1 parameters
S1-01
Disturb Function
Selection
0: Disabled
1: Enabled
2: Enabled, outputs the Disturb waveform during accel/
decel
0 to 2
0
A
−
−
680
S1-02
Disturb Function
Amplitude
Set the amplitude of the Disturb waveform as a
percentage of the frequency reference.
0.00 to
20.00
0.00%
A
−
−
681
S1-03
Disturb Step
Sets the step applied at the end of disturb acceleration or
deceleration as a percentage of the Disturb amplitude in
S1-02.
0 to 50
0%
A
−
−
682
S1-04
Disturb Deceleration
Time
Sets the deceleration time for the Disturb function.
0.0 to
120.0
0.0 s
A
−
−
683
S1-05
Disturb Acceleration
Time
Sets the acceleration time for the Disturb function.
0.0 to
120.0
0.0 s
A
−
−
684
S2: Frequency Reference Gain Settings
S2 parameter determines how much to reduce or amplify the frequency reference.
S2-01
Frequency Reference
Gain
Determines how much to reduce or amplify the
frequency reference. The frequency reference cannot
exceed the upper limit set to d2-01.
0.0 to
1000.0
100.0%
A
A
A
690
S2-02
Frequency Reference
Gain Change Ramp
Determines the time required to accelerate from 0.00%
to the gain level set in S2-01.
0.0 to
600.0
0.0 s
A
A
A
691
S3: Braking Transistor and V/f Ratio Gain
Use S3 parameters to add gain to the braking transistor or V/f ratio.
S3-01
Braking Transistor
Operation Selection
0: During run only
1: Always enabled
0, 1
0
A
A
A
6A0
S3-02
Braking Transistor
Operation Voltage Level
Sets the voltage level that triggers drive built-in the
braking transistor.
300 to 400 380 Vdc
A
A
A
6A1
S3-03
V/f Gain Enable/Disable
Enables and disables the V/f gain setting in MEMOBUS
register 03H.
0: Disabled
1: Enabled
0, 1
0
A
−
−
6A2
S3-04
V/f Gain Change Time
Sets the drive uses to change the V/f gain set in
MEMOBUS register 03H.
0.0 to 10.0
0.5 s
A
−
−
6A3
S4: KEB Mode Selection
S4 parameters define the conditions for how the KEB function operate.
S4-01
KEB Mode Selection
0: KEB disabled
1: DC bus voltage control (KEB 1)
2: Synchronous accel/decel (KEB 2)
3: Power KEB (KEB 3)
0 to 3
0
A
A
A
6B0
S4-02
KEB Start/End Voltage
Determines how the KEB start and end voltage in
parameters S4-03 and S4-06 are set.
0: Set as a Percentage of E1-01
1: Set as a percentage of the DC bus voltage before KEB
was triggered.
0, 1
0
A
A
A
6B1
S4-03
KEB Start Voltage
Determines the voltage level in the DC bus that will
trigger KEB. The setting value depends on the selection
in parameter S4-02. A setting of 200.0% essentially
disables S4-03.
0.0 to
200.0
200.0%
A
A
A
6B2
S4-04
KEB Start dV/dt Level
Sets the level of voltage fluctuation in the DC bus that
triggers KEB.
0 to 10000 0 Vdc/s
A
A
A
6B3
S4-05
KEB Start dV/dt filter
Sets the time required for the voltage fluctuation level
defined in S4-04 to trigger KEB.
0 to 50
20 ms
A
A
A
6B4
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...