5.7 H: Terminal Functions
168
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Setting 7E: Forward Reverse Detection (V/f Control with Simple PG Feedback)
When a digital input is programmed for this function, the input determines the direction of the speed feedback signal for
V/f Control with PG feedback. If the input is open, the speed feedback signal is considered to be forward, if the input is
closed, it is considered to be in reverse.
Refer to C5: Automatic Speed Regulator (ASR) on page 138
for details.
◆
H2: Multi-Function Digital Outputs
■
H2-01 to H2-03: Terminal MA, MB and MC, P1-C1 and P2-C2 Function Selection
The drive has three multi-function output terminals. Set parameters H2-01 to H2-03 between 0 and 192 to assign
functions to these terminals. Default values are listed in the following table.
Note:
If not using an input terminal or if using it in the through-mode, be sure to set that terminal to “F”.
Table 5.17 Multi-Function Output Terminal Settings
Setting 0: During Run
Output closes when the drive is outputting a voltage.
No.
Parameter Name
Setting Range
Default
H2-01
Terminal MA, MB and MC Function Selection (relay)
0 to 152
E: Fault
H2-02
Terminal P1-C1 Function Selection (open-collector)
0 to 152
0: During Run
H2-03
Terminal P2-C2 Function Selection (open-collector)
0 to 152
2: Speed Agree 1
Setting
Function
Page
Setting
Function
Page
0
During Run
1A
During Reverse Operation
1
Zero Speed
1B
During Baseblock (N.C.)
2
Speed Agree 1
1C
Motor 2 Selection
3
User Set Speed Agree 1
1E
Restart Enabled
4
Frequency Detection 1
1F
Motor Overload Alarm (oL1)
5
Frequency Detection 2
20
Heatsink Overheat Pre alarm (oH)
6
Drive Ready
30
During Torque Limit
7
DC Bus Undervoltage
37
During Frequency Output
8
During Baseblock (N.O.)
39
Watt Hour Pulse Output
9
Frequency Reference Source
3C
LOCAL/REMOTE Status
A
Run Command Source
3D
During Speed Search
B
Torque Detection 1 (N.O.)
3E
PID Feedback Low
C
Frequency Reference Loss
3F
PID Feedback High
D
Braking Resistor Fault
4A
During KEB Operation
E
Fault
4B
During Short-Circuit Braking
F
Not used/Through Mode
4C
During Fast-stop
10
Alarm
50
Disturb Function Up
11
Reset Command Active
51
Disturb Function Enabled/Disabled
12
Timer Output
52
Uv during KEB
13
Speed Agree 2
100 to 10D
Inverse Output of Setting 0 to D
14
User Set Speed Agree 2
10F to 11B
Inverse Output of Setting F to 1B
15
Frequency Detection 3
11E to 120
Inverse Output of Setting 1E to 20
16
Frequency Detection 4
137, 138
Inverse Output of Setting 37 and 38
17
Torque Detection 1 (N.C.)
13C to 14C
Inverse Output of Setting 3C to 4C
18
Torque Detection 2 (N.O.)
14F to 152
Inverse Output of Setting 14F to 152
19
Torque Detection 2 (N.C.)
Status
Description
Open
Drive is stopped.
Closed
A Run command is input or the drive is during deceleration or during DC injection.
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...