F1-10, F1-11: Excessive Speed Deviation Detection Level, Delay Time
F1-10 sets the detection level for a speed deviation (dEv) fault as a percentage of the maximum output frequency. The
speed feedback has to exceed this level for longer than the time set in F1-11 before a fault is detected. Speed deviation is
the difference between actual motor speed and the frequency reference command.
■
F1-14: PG Open-Circuit Detection Time
Sets the time required to detect PGo if no pulse signal is present at terminal RP.
◆
F6: Communication Option Card
These parameters are to configure communication option cards and communication fault detection methods.
■
F6-01: Communications Error Operation Selection
Determines drive operation if a communication error occurs.
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
■
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
Setting 0: Always Detected
Setting 1: Detection During Run Only
■
F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option (EF0).
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
No.
Parameter Name
Setting Range
Default
F1-10
Excessive Speed Deviation Detection Level
0 to 50%
10%
F1-11
Excessive Speed Deviation Detection Delay Time
0.0 to 10.0 s
0.5 s
No.
Parameter Name
Setting Range
Default
F1-14
PG Open-Circuit Detection Time
0.0 to 10.0 s
2.0 s
No.
Parameter Name
Setting Range
Default
F6-01
Communications Error Operation Selection
0 to 3
1
No.
Parameter Name
Setting Range
Default
F6-02
External Fault from Comm. Option Detection Selection
0 or 1
0
No.
Parameter Name
Setting Range
Default
F6-03
External Fault from Comm. Option Operation Selection
0 to 3
1
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...