4.1 FT82 SERVOPACKs with Analog Voltage/Pulse Train References
4
Parameter Li
s
t
s
4-23
Pn50D
2
Input Signal Selections
4
0000h to
FFFFh
–
8888h
–
After
restart
Setup
–
Continued on next page.
Continued from previous page.
Parameter
No.
Siz
e
Name
Setting
Range
Setting
Unit
Default
Setting
Applicable
Motors
When
Enabled
Classi-
fication
Refer-
ence
n.
X
/ZCLAMP (Zero Clamping Input) Signal Allocation
Applicable
Motors
Reference
0
Active when CN1-40 input signal is ON (closed).
All
*1
1
Active when CN1-41 input signal is ON (closed).
2
Active when CN1-42 input signal is ON (closed).
3
Active when CN1-43 input signal is ON (closed).
4
Active when CN1-44 input signal is ON (closed).
5
Active when CN1-45 input signal is ON (closed).
6
Active when CN1-46 input signal is ON (closed).
7
The signal is always active.
8
The signal is always inactive.
9
Active when CN1-40 input signal is OFF (open).
A
Active when CN1-41 input signal is OFF (open).
B
Active when CN1-42 input signal is OFF (open).
C
Active when CN1-43 input signal is OFF (open).
D
Active when CN1-44 input signal is OFF (open).
E
Active when CN1-45 input signal is OFF (open).
F
Active when CN1-46 input signal is OFF (open).
n.
X
/INHIBIT (Reference Pulse Inhibit Input) Signal Allocation
Applicable
Motors
Reference
0 to F
The allocations are the same as the /ZCLAMP
(Zero Clamping Input) signal allocations.
All
*1
n.
X
/G-SEL (Gain Selection Input) Signal Allocation
Applicable
Motors
Reference
0 to F
The allocations are the same as the /ZCLAMP
(Zero Clamping Input) signal allocations.
All
*1
n.X
Reserved parameter (Do not change.)