3.5 FT83 SERVOPACKs with Analog Voltage/Pulse Train References
3.5.4 INDEXER Alarm Displays and Troubleshooting
3
Maintenance
3-235
E17A
A.C90 or
A.040
Initial Communi-
cation
Alarm
between
INDEXER Mod-
ule and SERVO-
PACK
(Detected only
when control
power supply is
turned ON.)
•
The INDEXER
failed in parame-
ter calculation
during initial com-
munications with
the SERVOPACK
when the control
power was turned
ON.
This can happen in
the following
cases:
•
When a parame-
ter has been
changed while
the encoder is
not connected
•
When a parame-
ter has been
changed during
occurrence of
A.040 alarm
•
Connect the
encoder and then
change the parame-
ter.
•
Cancel the A.040
alarm and then
change the parame-
ter.
(If the alarm display
is other than A.E00,
it can be reset by
turning the power
OFF and back ON.)
Gr.1
N/A
E19A
A.EF9
Program Table
Checksum
Alarm
(Detected only
when control
power supply is
turned ON.)
The program table
stored in flash mem-
ory was not
recorded properly.
(This alarm can
occur if the control
power supply is
turned OFF while the
program table is
being saved or ini-
tialized.)
•
Initialize the pro-
gram table. (Fn063)
•
If the problem is not
solved, correct the
program table.
Gr.1
Available
*1
E1AA
A.EF9
Program Table
Version
Unmatched
(Detected only
when the control
power is ON.)
The combination of
the firmware version
and the program
table version is
wrong.
•
Change the firm-
ware version.
•
Change the pro-
gram table version
to match the firm-
ware version.
Gr.1
Available
*1
E1BA
A.EF9
Program Out-
of-range Alarm
(Detected only
when control
power supply is
turned ON.)
A value set in the
program table is not
within the allowed
setting range.
•
Change the firm-
ware version.
•
Change the pro-
gram table version
to match the firm-
ware version.
Gr.1
Available
*1
E1CA
A.EF9
Zone Table
Checksum
Alarm
(Detected only
when control
power supply is
turned ON.)
The zone table
stored in flash mem-
ory was not
recorded properly.
(This alarm can
occur if the control
power supply is
turned OFF while the
zone table is being
saved or initialized.)
•
Initialize the zone
table. (Fn064)
•
If the problem is not
solved, correct the
zone table.
Gr.1
Available
*2
Continued on next page.
Continued from previous page.
Error
Number
Alarm
Number
Alarm Name
Meaning
Corrective Action
Servo-
motor
Stop
Method
Alarm
Reset