3.3 FT82 SERVOPACK with MECHATROLINK-III Communications References
3.3.5 List of Warnings
3
Maintenance
3-129
*
If using the commands for the MECHATROLINK-III standard servo profile, the warning will automatically be
cleared after the correct command is received. If you use MECHATROLINK-II-compatible profile commands, send
an ALM_CLR (Clear Warning or Alarm) command to clear the warning.
A.942
Speed Ripple Com-
pensation Information
Disagreement
The speed ripple compensation information stored in
the encoder does not agree with the speed ripple com-
pensation information stored in the SERVOPACK.
Required.
A.94A
Data Setting Warning 1
(Parameter Number
Error)
There is an error in the parameter number for a Data
Setting Warning 1 (Parameter Number) command.
Automatically
reset.
*
A.94b
Data Setting Warning 2
(Out of Range)
The command data is out of range.
Automatically
reset.
*
A.94C
Data Setting Warning 3
(Calculation Error)
A calculation error was detected.
Automatically
reset.
*
A.94d
Data Setting Warning 4
(Parameter Size)
The data sizes do not match.
Automatically
reset.
*
A.94E
Data Setting Warning 5
(Latch Mode Error)
A latch mode error was detected.
Required.
A.95A
Command Warning 1
(Unsatisfied Com-
mand Conditions)
A command was sent when the conditions for sending
a command were not satisfied.
Automatically
reset.
*
A.95b
Command Warning 2
(Unsupported Com-
mand)
An unsupported command was sent.
Automatically
reset.
*
A.95d
Command Warning 4
(Command Interfer-
ence)
There was command interference, particularly latch
command interference.
Automatically
reset.
*
A.95E
Command Warning 5
(Subcommand Not
Possible)
The subcommand and main command interfere with
each other.
Automatically
reset.
*
A.95F
Command Warning 6
(Undefined Command)
An undefined command was sent.
Automatically
reset.
*
A.960
MECHATROLINK
Communications
Warning
A communications error occurred during
MECHATROLINK communications.
Required.
A.971
Undervoltage
This warning occurs before an A.410 alarm (Undervolt-
age) occurs. If the warning is ignored and operation is
continued, an alarm may occur.
Required.
A.97A
Command Warning 7
(Phase Error)
A command that cannot be executed in the current
phase was sent.
Automatically
reset.
*
A.97b
Data Clamp Out of
Range
The set command data was clamped to the minimum or
maximum value of the allowable setting range.
Automatically
reset.
*
A.9A0
Overtravel
Overtravel was detected while the servo was ON.
Required.
A.9b0
Preventative Mainte-
nance Warning
One of the consumable parts has reached the end of its
service life.
Required.
Continued from previous page.
Warning
Number
Warning Name
Meaning
Resetting