3.4 Command Option Attachable-type FT82 SERVOPACKs with INDEXER Modules
3.4.4 INDEXER Module Alarm Displays and Troubleshooting
3
Maintenance
3-179
E1AA
A.AEF
Program Table
Version
Unmatched
(Detected only
when the control
power is ON.)
The combination of
the firmware version
and the program
table version is
wrong.
•
Change the firm-
ware version.
•
Change the pro-
gram table version
to match the firm-
ware version.
Gr.1
Available
*1
E1BA
A.AEF
Program Out-
of-range Alarm
(Detected only
when control
power supply is
turned ON.)
A value set in the
program table is not
within the allowed
setting range.
•
Change the firm-
ware version.
•
Change the pro-
gram table version
to match the firm-
ware version.
Gr.1
Available
*1
E1CA
A.AEF
Zone Table
Checksum
Alarm
(Detected only
when control
power supply is
turned ON.)
The zone table
stored in flash mem-
ory was not
recorded properly.
(This alarm can
occur if the control
power supply is
turned OFF while the
zone table is being
saved or initialized.)
•
Initialize the zone
table with the
ZONEINIT com-
mand or FnB07.
*2
•
If the problem is not
solved, correct the
zone table.
Gr.1
Available
*2
E1DA
A.AEF
ZONE Table
Version
Unmatched
(Detected only
when the control
power supply is
turned ON.)
The combination of
the firmware version
and the ZONE table
version is wrong.
•
Change the firm-
ware version.
•
Change the ZONE
table version to
match the firmware
version.
Gr.1
Available
*2
E1EA
A.AEF
Zone Table Out-
of-range Alarm
(Detected only
when control
power supply is
turned ON.)
A value set in the
zone table is not
within the allowed
setting range.
•
Change the firm-
ware version.
•
Change the ZONE
table version to
match the firmware
version.
Gr.1
Available
*2
E1FA
A.AEF
JOG Speed
Table Check-
sum Alarm
(Detected only
when control
power supply is
turned ON.)
The JOG speed
table stored in flash
memory was not
recorded properly.
(This alarm can
occur if the control
power supply is
turned OFF while the
JOG speed table is
being saved or ini-
tialized.)
•
Initialize the JOG
speed table with the
JSPDINIT com-
mand or FnB08.
•
If the problem is not
solved, correct the
JOG speed table.
Gr.1
Available
*3
E21A
A.AEF
JOG Speed
Table Version
Unmatched
(Detected only
when the control
power supply is
turned ON.)
The combination of
the firmware version
and the JOG speed
table version is
wrong.
•
Change the firm-
ware version.
•
Change the JOG
speed table version
to match the firm-
ware version.
Gr.1
Available
*3
Continued on next page.
Continued from previous page.
Serial
Command
Negative
Response
Alarm
Number
Alarm Name
Meaning
Corrective Action
Servo-
motor
Stop
Method
Alarm
Reset