12.3 SERVOPACK Main Circuit Wires
12.3.1 Three-Phase, 200-VAC Wires for
Σ
-7S SERVOPACKs
12-10
12.3
SERVOPACK Main Circuit Wires
This section describes the main circuit wires for SERVOPACKs.
Note: To use 600-V heat-resistant polyvinyl chloride-insulated wire (HIV), use the following table as reference for the
applicable wires.
•
The specified wire sizes are for three bundled leads when the rated current is applied with a surrounding
air temperature of 40
°
C.
•
Select the wires according to the surrounding air temperature.
12.3.1
Three-Phase, 200-VAC Wires for
Σ
-7S SERVOPACKs
These specifications are based on IEC/EN 61800-5-1, UL 61800-5-1, and CSA C22.2 No.274.
1. To comply with UL standards, use UL-compliant wires.
2. Use copper wires with a rated temperature of 75
°
or higher.
3. Use wires with a rated withstand voltage of 300 V or higher.
Important
SERVOPACK
Model: SGD7S-
Terminal Symbols
Wire Size
Screw
Size
Tightening
Torque
[N
⋅
m]
R70A
Main Circuit Power
Supply Cables
L1, L2, L3
AWG16 (1.25 mm
2
)
−
−
Servomotor Main Cir-
cuit Cables
*
U, V, W
Control Power Supply
Cables
L1C, L2C
External Regenerative
Resistor Cables
B1/ , B2
Ground cable
AWG14 (2.0 mm
2
) or larger
M4
1.2 to 1.4
R90A
Main Circuit Power
Supply Cables
L1, L2, L3
AWG16 (1.25 mm
2
)
−
−
Servomotor Main Cir-
cuit Cables
*
U, V, W
Control Power Supply
Cables
L1C, L2C
External Regenerative
Resistor Cables
B1/ , B2
Ground cable
AWG14 (2.0 mm
2
) or larger
M4
1.2 to 1.4
1R6A
Main Circuit Power
Supply Cables
L1, L2, L3
AWG16 (1.25 mm
2
)
−
−
Servomotor Main Cir-
cuit Cables
*
U, V, W
Control Power Supply
Cables
L1C, L2C
External Regenerative
Resistor Cables
B1/ , B2
Ground cable
AWG14 (2.0 mm
2
) or larger
M4
1.2 to 1.4
2R8A
Main Circuit Power
Supply Cables
L1, L2, L3
AWG16 (1.25 mm
2
)
−
−
Servomotor Main Cir-
cuit Cables
*
U, V, W
Control Power Supply
Cables
L1C, L2C
External Regenerative
Resistor Cables
B1/ , B2
Ground cable
AWG14 (2.0 mm
2
) or larger
M4
1.2 to 1.4
Continued on next page.
+
+
+
+