![wtw TresCon UNO A111 Скачать руководство пользователя страница 89](http://html1.mh-extra.com/html/wtw/trescon-uno-a111/trescon-uno-a111_operating-manual_1000694089.webp)
TresCon UNO
Operation
5 - 33
ba43134e08
05/2017
Characteristic curves
Through the selection of the
Start value
and
End value
, the proportional
controller can be operated with a positive or negative characteristic cur-
ve.
Positive characteristic curve:
Select the
End value
to be higher than the
Start value
.
The turn-on duration or frequency increases with an increasing mea-
sured value (see page 5-34).
Negative characteristic curve:
Select the
End value
to be lower than the
Start value
.
The turn-on duration or frequency decreases with an increasing
measured value (see page 5-35).
The maximum values for the pulse width or switching frequency are
assigned to the
End value
and the minimum values for turn-on duration
or frequency are assigned to the
Start value
.
Fig. 5-9
Positive characteristic curve
Fig. 5-10 Negative characteristic curve
Measured value
Switching frequency f or
Pulse
v
width
End value
Start value
Max.
Min.
Measured value
Start value
End value
Max.
Min.
Switching frequency f or
Pulse
v
width
Содержание TresCon UNO A111
Страница 2: ...2 ba43134e08 05 2017 TresCon UNO Copyright 2017 Xylem Analytics Germany GmbH Printed in Germany...
Страница 6: ...Inhaltsverzeichnis TresCon UNO 0 4 ba43134e08 05 2017 9 1 Abbreviations 9 1 9 2 Index 9 1...
Страница 18: ...Safety TresCon UNO 2 4 ba43134e08 05 2017...
Страница 56: ...Initial commissioning TresCon UNO 4 4 ba43134e08 05 2017...
Страница 133: ...TresCon UNO Operation 5 77 ba43134e08 05 2017 9 Select Yes or No with 68 and confirm with 3...
Страница 167: ...TresCon UNO Maintenance 6 11 ba43134e08 05 2017 6 Leave the menu with 4...
Страница 202: ...Appendix TresCon UNO 8 24 ba43134e08 05 2017...
Страница 207: ......