Relays as limiting value indicators
Function
The characteristics of the limit value indicator are defined by the set-
tings,
Climit
,
hysteresis
and
td.
The fundamentals of the function are
described in the introductory chapter (see section 5.3.3).
Settings
Setting
Selection/Values
Explanation
Climit
within the measuring
range (depending on
the analyzer module)
Upper or lower limi-
ting value.
Note:
Minimum distance
between the upper
and lower limiting
value in the case of
monitoring with 2
relays:
10% of the measuring
range
Hysteresis
0 ... 10 %
of the
measuring range
Hysteresis for upper
or lower limiting value
td
0 ... 3600 s
Switching delay:
The time period for
which a limiting value
must be exceeded
before the relay ope-
rates.
Prevents frequent
switching for measu-
red values that are
close to the limiting
value.
Action
Normally closed
Normally open
Relay action (see
section 5.3.1)
Response with stop
Active
Passive
In Stop mode, the
relay switches to the
selected condition.
Also in the case of
AutoCal
,
AutoClean
etc.
Hold
The switching condi-
tion remains
unchanged.
Содержание TresCon UNO A111
Страница 2: ...2 ba43134e08 05 2017 TresCon UNO Copyright 2017 Xylem Analytics Germany GmbH Printed in Germany...
Страница 6: ...Inhaltsverzeichnis TresCon UNO 0 4 ba43134e08 05 2017 9 1 Abbreviations 9 1 9 2 Index 9 1...
Страница 18: ...Safety TresCon UNO 2 4 ba43134e08 05 2017...
Страница 56: ...Initial commissioning TresCon UNO 4 4 ba43134e08 05 2017...
Страница 133: ...TresCon UNO Operation 5 77 ba43134e08 05 2017 9 Select Yes or No with 68 and confirm with 3...
Страница 167: ...TresCon UNO Maintenance 6 11 ba43134e08 05 2017 6 Leave the menu with 4...
Страница 202: ...Appendix TresCon UNO 8 24 ba43134e08 05 2017...
Страница 207: ......