09 SIGNAL FILTER TC:
[*2 (0.01,7200)] This menu item defines the time constant for the Lag Filter for
the pond/tail level signal. When this value is left at 0.01, the filter is basically turned off. This number
should only be increased if the level signal is noisy.
10 RAISE/LOWER RATE:
[*1 (0.01,1000)] This menu item defines the rate at which the RAISE and
LOWER commands adjust the pond/tail level reference.
11 LEVEL GATE RATE:
[*0.05 (0.001,100)] This menu item defines the rate at which the level reference
is adjusted by the RAISE and LOWER commands.
19 REMOTE LEVEL CTRL
This menu contains items related to remote level control.
01 REM LEVEL ENABLED:
[MONITOR] This menu item displays when remote level control is enabled.
02 REM LVL ANLG IN ENABLED:
[MONITOR] It displays if the accepted remote level value will be from
analog input
03 RMT LVL ANALOG IN:
[MONITOR] It displays the value of the Remote level Control analog input
(scaled)
04 REM LVL MODBUS ENABLED
: [MONITOR] It displays if the accepted remote level value will be from
Modbus
05 REMOTE LEVEL REFERENCE
:[MONITOR] Is displays the actual value of the Remote level reference
06 AI VALUE @ 4 mA
:[*0(-200,200)] Configure the value of the Remote level reference when the current
input is 4 mA
07 AI VALUE @ 20 mA
:[*100(-200,200)] Configure the value of the Remote level reference when the
current input is 20 mA
20 GAINS
This menu contains items related to the gains in the 2301E-HT digital control.
01 DROOP:
[*5 (0,10)] This menu item defines the droop percent in the 2301E-HT.
02 OFFLINE P GAIN:
[*1 (0.001,50)] This menu item defines the proportional gain used when the unit is
off-line or in isochronous mode.
03 OFFLINE I GAIN:
[*0.2 (0.001,50)] This menu item defines the integral gain used when the unit is off-
line or in isochronous mode.
04 OFFLINE D GAIN:
[*100 (0.001, 50)] This menu item defines the derivative gain used when the unit is
off-line or in isochronous mode. In order to disable this gain this parameter must stay on 100.
05 ONLINE P GAIN:
[*1.0 (0.001,50)] This menu item defines the proportional gain used when the unit is
on-line/droop mode.
06 ONLINE I GAIN:
[*0.2 (0.001,50)] This menu item defines the integral gain used when the unit is on-
line/droop mode.
07 ONLINE D GAIN:
[*100 (0.001, 50)] This menu item defines the derivative gain used when the unit is
on-line/droop mode. In order to disable this gain this parameter must stay on 100.
08 DISABLE FEED FWD?:
[TRUE or *FALSE] This menu item disables Feed Forward when tuned to
TRUE. This menu item should be left FALSE in most applications.
09 FEED FORWARD GAIN:
[*1 (0,5)] This menu item defines the Feed Forward Gain. This gain picks the
derivative of the on-line speed setpoint and moves the gate in the proper direction This is used in on-
line/droop mode.
10 TEMPORARY COMP:
[*0.05 (0,10)] This menu item defines the temporary compensation adjustment.
This is used off-line or in isochronous mode.
11 ERROR GAIN:
[*1 (1,100)] This menu item defines the Error Gain. This gain multiplies the P, I and D
gain. This is used in on-line/droop mode.
21 GATE TIMER
This menu contains items related to the gate timer function.
01 TRN ON GATE TIMER:
[TRUE or *FALSE] This menu item activates the gate timer function.
02 GATE TIME (SEC):
[MONITOR] This menu item displays, in seconds, the gate time from 0% to 100%
or 100% to 0%.
03 RESET GATE TIME:
[TRUE or *FALSE] This menu item resets the gate time timer back to 0 seconds.
04 GOTO 5% GATE POS:
[TRUE or *FALSE] This menu item forces the gates to 5% when the 2301E-
HT is in manual control mode.