Manual 35092
2301E-HT Hydro (Francis Turbines)
Woodward
53
05 GP SW1 - LO DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the gate position should be
less than LO SET to de-energize the relay when configured to increasing or to energize the relay when
configured to decreasing.
06 SW2 - DECREASING?:
[TRUE or *FALSE] This determines if Gate Position Switch #2 is an
increasing switch or a decreasing switch. If the switch should trigger when the gates are closing, then this
value should be set to TRUE. If the switch should trigger when the gates are opening, then this value
should be set to FALSE.
07 GP SW2 - HI SET:
[*50.0 (0.0,100.0)] This is the high set point for the gate position switch. When the
switch is increasing, this set point is the trip point of the gate position switch. When the switch is
decreasing, this set point is the reset point of the gate position switch.
08 GP SW2 - HI DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the gate position should be
greater than HI SET to energize the relay when configured to increasing or to de-energize the relay when
configured to decreasing.
09 GP SW2 - LOW SET:
[*45.0 (0.0,100.0)] This is the low set point for the gate position switch. When
the switch is increasing, this set point is the reset point of the gate position switch. When the switch is
decreasing, this set point is the trip point of the gate position switch.
10 GP SW2 - LO DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the gate position should be
less than LO SET to de-energize the relay when configured to increasing or to energize the relay when
configured to decreasing.
29 CONFIG kW SW
If any relay output is configured as kW switch, then the kW switches are configured here. If no relay
outputs are configured as kW switches, then this menu does not affect the control and can be skipped.
01 SW1 - DECREASING?:
[TRUE or *FALSE] This determines if kW Switch #1 is an increasing switch or
a decreasing switch. If the switch should trigger when the kW is decreasing, then this value should be set
to TRUE. If the switch should trigger when the kW is increasing, then this value should be set to FALSE.
02 kW SW1 - HI SET:
[*50 (0.0,100.0)] This is the high set point for the kW switch. When the switch is
increasing, this set point is the trip point of the kW switch. When the switch is decreasing, this set point is
the reset point of the kW switch.
03 kW SW1 - HI DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the kW should be greater
than HI SET to energize the relay when configured to increasing or to de-energize the relay when
configured to decreasing.
04 kW SW1 - LOW SET:
[*45.0 (0.0,100.0)] This is the low set point for the kW switch. When the switch
is increasing, this set point is the reset point of the kW switch. When the switch is decreasing, this set
point is the trip point of the kW switch.
05 kW SW1 - LO DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the kW should be less than
LO SET to de-energize the relay when configured to increasing or to energize the relay when configured
to decreasing.
06 SW2 - DECREASING?:
[TRUE or *FALSE] This determines if kW Switch #2 is an increasing switch or
a decreasing switch. If the switch should trigger when the kW is decreasing, then this value should be set
to TRUE. If the switch should trigger when the kW is increasing, then this value should be set to FALSE.
07 kW SW2 - HI SET:
[*50.0 (0.0,100.0)] This is the high set point for the kW switch. When the switch is
increasing, this set point is the trip point of the kW switch. When the switch is decreasing, this set point is
the reset point of the kW switch.
08 kW SW2 - HI DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the kW should be greater
than HI SET to energize the relay when configured to increasing or to de-energize the relay when
configured to decreasing.
09 kW SW2 - LOW SET:
[*45.0 (0.0,100.0)] This is the low set point for the kW switch. When the switch
is increasing, this set point is the reset point of the kW switch. When the switch is decreasing, this set
point is the trip point of the kW switch.
10 kW SW2 - LO DELAY:
[*0.0 (0.0, 600.0)] This is the time (in seconds) that the kW should be less than
LO SET to de-energize the relay when configured to increasing or to energize the relay when configured
to decreasing.
30 MON ANALOG OUT
This menu allows all analog output mA current signals to be monitored.